Leave Your Message

S13-M Fully Sealed Oil Immersed Transformer

Overview
With the continuous development of my country 's economic construction, the improvement of people 's living standards, the increase in electricity load and the increase in transformer equipment have led to large energy consumption and increased noise, seriously polluting the urban environment. For this reason, countries around the world are calling for and taking steps to  reduce energy consumption and improve the  urban environment. S13-MThe series three-phase distribution transformer is moreS9, S11Compared with the type, The no-load loss is reduced by 50% and 30% respectively, and the noise level is reduced by 5-8%.db.

    Scope of use

    S13-MType distribution transformer is suitable for three-phase 50HZ, 10KVVoltage level distribution system, for industrial Agricultural power distribution, power and lighting. Especially for reducing noise and improving the environment in cities. It is beneficial to environmental quality and reduce electricity operating costs.

    Model and its meaning

    product-description1

    Normal operating conditions of transformer

    ◆ Altitude not exceeding 1000mAmbient temperature:
    ◇ The highest temperature is +40℃;
    ◇ The average temperature of the hottest month is +30℃;
    ◇ The highest annual average temperature is +20℃;
    ◇ The lowest outdoor temperature is -25℃.

    Special conditions for use of transformers

    ◆Altitude not exceeding 1000mAmbient temperature:
    ◇The highest temperature is +40℃;
    ◇Minimum temperature -45℃.
    (Detailed instructions when ordering)

    Transformer product standards

    ◇ GB 1094. 1-2013  GB 1094.2-2013  JB/T 10088-2004
    ◇ GB 1094.3-2016  GB 1094.5-2008  JB/T 3837-2010
    ◇ GB/T 6451-2015  GB/T 7595-2008

    Structural features

    ◇ The guiding idea of the overall layout design is to summarize S9 and S11. Based on the experience of model design, we put product reliability first to ensure that the product meets the electrical performance, mechanical strength and heat dissipation requirements. Strength and other requirements.
    ◇ The core adopts 23ZH100High magnetic permeability silicon steel sheet stacked structure.
    ◇ Both high and low voltage coils are wound in a cylindrical manner.
    ◇ The body and assembly structure are all made of matureS9Type product structure.
    ◇ Oil tank and heat dissipation element adopt rectangular corrugated oil tank, 2000kVAand 2500kVAFixed or detachable expansion plate radiator tank can be selected according to user requirements.
    ◇ Component selectionS9andS11A proven component for a wide range of products.

    Main technical parameters

    Rated capacitance Voltage combination (kV) Join Group number No-load current (%) Short Circuit impedance (%) weight(kg) Dimensions(mm) gauge mm
    high pressure Low pressure Oil weight Total weight Length L Width B High H
    30 6 6.3 6.6 10 10.5 11 ±5% or ±2× 2.5% 0.4 Yyn0 Dyn11 80 4 65 250 705 445 850 400x400
    50 100 75 320 745 500 880 400x400
    63 110 85 375 775 515 965 400x400
    80 130 95 425 790 590 985 400x400
    100 150 100 480 820 640 1005 400x400
    125 170 110 540 835 710 1030 550x550
    160 200 120 625 865 740 1030 550x550
    200 240 145 750 1085 680 1110 550x550
    250 290 160 860 1175 755 1130 550x550
    315 340 175 980 1190 765 1175 550x550
    400 410 200 1180 1275 825 1210 660x660
    500 480 225 1350 1325 880 1280 660x660
    630 570 4.5 260 1580 1420 935 1315 660x660
    800 700 285 1835 1490 985 1375 820x820
    1000 830 350 2170 1690 1220 1395 820x820
    1250 970 410 2645 1825 1305 1460 820x820
    1600 1170 470 3240 1825 1270 1515 820x820
    2000 1380 540 2860 2085 1235 1715 1070x1070
    2500 1680 600 4435 2130 1255 1805 1070x1070

    Appearance and installation dimensions

    product-description2

    10kV class S13-M Dimensions of series oil-immersed distribution transformers

    Rated capacity (kVA) Appearance and installation dimensions(mm)
    L W H C1 C2
    30 750 643 974 400 400
    50 795 493 1013 400 400
    63 800 665 1050 400 400
    80 840 680 1075 400 400
    100 775 690 1100 550 550
    125 1260 900 1045 550 550
    160 1090 720 1140 550 550
    200 1180 780 1155 550 550
    250 1175 750 1180 550 550
    315 1315 890 1240 660 660
    400 1330 910 1280 660 660
    500 1390 930 1340 660 660
    630 1545 1030 1410 820 820
    800 1570 1020 1535 820 820
    1000 1800 1250 1430 820 820
    1250 1910 1130 1650 820 820
    1600 2010 1220 1740 820 820
    2000 2120 1280 1780 820 820
    2500 2450 1280 2720 1070 1070

    Ordering Instructions

    ◇ When ordering, please provide product model, rated capacity, high and low voltage rated voltage and high voltage tapping range, number of phases, frequency and connection group number.

    Leave Your Message