S(B)H15M Amorphous Alloy Distribution Transformer – High Efficiency, Low Loss, China Suppliers & Factory
Product Features
◇ GB/T10228-1997, GB6450-1986, JB/T10088-2004, GB4208-1993
◇ Rated high voltage: 10 (11, 10.5, 6.6, 6.3, 6)kV
◇ Rated low pressure: 0.4kV
◇ Connection group: Dynl1orYY
◇ High voltage tapping range: ±5% or ±2×2.5%
◇ Insulation level: LI75AC35/LI OAG5
◇ Frequency: 50Hz
Model meaning
Product performance parameters
| Rated capacity | Voltage combination (kV) | Link group label | No-load loss | Load loss | No-load current | Impedance voltage | ||
| high pressure | High pressure decomposition range(%) | Low pressure | ||||||
| 30 | 6 6.3 6.6 10 10.5 11 |
±2×2.5 ±5 |
0.4 | Dyn11 Yyn0 |
33 | 630/600 | 1.5 | 4 |
| 50 | 43 | 910/870 | 1.2 | |||||
| 63 | 50 | 1090/1040 | 1.1 | |||||
| 80 | 60 | 1310/1250 | 1 | |||||
| 100 | 75 | 1580/1500 | 0.9 | |||||
| 125 | 85 | 1890/1800 | 0.8 | |||||
| 160 | 100 | 2310/2200 | 0.6 | |||||
| 200 | 120 | 2730/2600 | 0.6 | |||||
| 250 | 140 | 3200/3050 | 0.6 | |||||
| 315 | 170 | 3830/3850 | 0.5 | |||||
| 400 | 200 | 4520/4300 | 0.5 | |||||
| 500 | 240 | 5410/5150 | 0.5 | |||||
| 630 | 320 | 6200 | 0.3 | 4.5 | ||||
| 800 | 380 | 7500 | 0.3 | |||||
| 1000 | 450 | 10300 | 0.3 | |||||
| 1250 | 530 | 12000 | 0.2 | |||||
| 1600 | 630 | 14500 | 0.2 | |||||
| 2000 | 750 | 18300 | 0.2 | 5 | ||||
| 2500 | 21200 | 0.2 | 5 | |||||
Note: Due to continuous product updates, the parameters in the table may change. Please refer to the parameters provided when ordering.
Note 1: When the core is a three-phase column, a Yyn0 connection group can also be used as needed.
Note 2: For three-phase transformers with a rated capacity of 500kVA and below, the load loss values above the slash in the table are applicable to the Dyn11 connection group, and the load loss values below the slash are applicable to the Yyn0 connection group.
Note 3: Other loss values may be selected if required by the user.
Note 4: Three-phase transformers with other high voltage tapping ranges can be provided according to user needs.
Product performance parameters (continued)
| Rated capacity | Voltage combination (kV) | Link group label | No-load loss | Load loss | No-load current | Impedance voltage | ||
| high pressure | High pressure decomposition range(%) | Low pressure | ||||||
| 30 | 20 | ±2×2.5 ±5 |
0.4 | Dyn11 | 40 | 690/660 | 1.5 | 5.5 |
| 50 | 55 | 1010/960 | 1.2 | |||||
| 63 | 65 | 1200/1150 | 1.1 | |||||
| 80 | 75 | 1440/1370 | 1 | |||||
| 100 | 90 | 1720/1650 | 0.9 | |||||
| 125 | 100 | 2080/1980 | 0.8 | |||||
| 160 | 120 | 2540/2420 | 0.6 | |||||
| 200 | 145 | 3000/2860 | 0.6 | |||||
| 250 | 165 | 3520/3350 | 0.6 | |||||
| 315 | 200 | 4210/4010 | 0.5 | |||||
| 400 | 240 | 4970/4730 | 0.5 | |||||
| 500 | 290 | 5940/5560 | 0.5 | |||||
| 630 | 370 | 6820/8250 | 0.3 | 6 | ||||
| 800 | 450 | 11330 | 0.3 | |||||
| 1000 | 530 | 13200 | 0.3 | |||||
| 1250 | 620 | 15950 | 0.2 | |||||
| 1600 | 750 | 19140 | 0.2 | |||||
| 2000 | 900 | 22220 | 0.2 | |||||
| 2500 | 1080 | 21200 | 0.2 | |||||
Note 1: When the core is three-phase and three-column, it can also be used as needed.Yyn0Connection group.
Note 2: For rated capacity of 500kv For transformers below 1000A, the load loss values above the slash in the table apply to Dyn11The load loss values below the slash apply to the connected groupYyn0 Connection group.
Note 3: Other loss values may be selected if required by the user.
Note 4: Transformers with other high voltage tapping ranges can be provided according to user needs.
Note 5: The performance parameters in the table are also applicable to high voltage dual voltage 20 (10)kVTransformer
Note 6: Due to continuous product updates, the parameters in the table may change. Please refer to the parameters provided when ordering.
Products meet standards
◇ GB 1094. 1-1996 Power transformers Part 1 General
◇ GB1094.2-1996 Temperature rise of the second part of power transformer
◇ GB1094.3-2003 Power transformers - Part 3 Insulation levels, insulation tests and external insulation air gaps
◇ GB1094.5-2008 Power transformer part 5 short circuit capability
◇ GB/T25446-2010 Technical parameters and requirements of oil-immersed amorphous alloy core distribution transformers
◇ GB311. 1-1997 Insulation coordination of high voltage power transmission and transformation equipment
◇ IEG 60076 Power Transformer
◇ ANSI/C57.12.00 General technical requirements for oil-immersed distribution, power and voltage regulating transformers
Frequently Asked Questions (FAQ)
Q1: What high voltage combinations are available for this transformer series?
The transformer supports high voltage ratings including 6kV, 6.3kV, 6.6kV, 10kV, 10.5kV, 11kV, and up to 20kV, paired with a standard low voltage output of 0.4kV.
Q2: Which connection groups are available for ordering?
Standard options include Dyn11 and Yyn0 connection groups depending on core structure and customer specifications.
Q3: Can the high-voltage tapping range be customized?
Yes, standard tapping ranges are ±5% or ±2×2.5%, but custom high voltage tapping ranges can be accommodated upon request.
Q4: What international and national standards does this product meet?
This product complies with standard guidelines including GB 1094 series, GB/T25446-2010, IEC 60076, and ANSI/C57.12.00.
Q5: Are loss performance parameters subject to modification?
Yes, alternative loss parameters or special efficiency requirements can be customized to align with project and grid standards.