Overview

,

The KYN28-24 Armored Removable AC Metal-Enclosed Switchgear, manufactured in China, is designed for three-phase AC 50Hz power systems. This high-quality switchgear is ideal for the reception and distribution of electrical energy, providing effective control, protection, and monitoring of circuits. As a leading product from top suppliers and factories in the industry, this switchgear adheres to several vital standards, including GB3906-2006 for 3.6-40.5kV AC Metal-Enclosed Switchgear and Controlgear, GB/T11022 outlining Common Technical Requirements for High Voltage Switchgear and Controlgear, IEC62271:200 for AC Metal-Enclosed Switchgear and Controlgear with nominal voltage over 1kV and below 52kV, and DL/T404 which sets the Technical Conditions for Ordering Indoor AC High Voltage Switchgear.

,

    Model and Definitions

    Model and Definitions Diagram

    Application Conditions

    • Ambient Air Temperature: Maximum temperature 40℃, minimum temperature -15℃;
    • Relative Humidity: Daily average not exceeding 95%, daily average vapor pressure not exceeding 2.2 kPa; monthly average not exceeding 90%, monthly average vapor pressure not exceeding 1.8 kPa;
    • Altitude: 1000m and below;
    • Seismic Intensity: Not exceeding 8 degrees;
    • Surrounding air should not be significantly polluted by corrosive or flammable gases, water vapor, etc.;
    • No frequent severe vibration in the area;
    • If used under conditions exceeding the normal environmental conditions specified in GB3906, it should be negotiated between the user and the manufacturer.

    Technical Specifications

    Items Units Data
    Nominal Voltage kV 24
    Rated Frequency Hz 50
    Circuit Breaker Rated Currency A 630, 1250, 1600, 2000, 2500, 3150, 4000
    Switch Cabinet Rated Currency A 630, 1250, 1600, 2000, 2500, 3150, 4000
    Rated Dynamic Stability Current(4s) kA 16, 20, 25, 31.5, 40, 50
    Rated Stability Current (Peak) kA 40, 50, 63, 80, 100, 125
    Rated Short-circuit Breaking Current kA 16, 20, 25, 31.5, 40, 50
    Rated Circuit Making Current (Peak) kA 40, 50, 63, 80, 100, 125
    Nominal Insulation Level 1min Power Frequency Withstand Voltage Between Poles, Between Pole and Ground kV 65
    Breakdown Voltage between Poles kV 79
    Lightning Impulse Withstand Voltage (Peak) Between Poles, Between Pole and Ground kV 125
    Breakdown Voltage Between Poles kV 145
    Level of Protection The shell is IP4X, and the isolation chamber and circuit breaker room are IP2X when the door is open.
    Note: The short-circuit capacity of the current transformer is considered separately.

    Structural Features of Products

    • Structure of the Switchgear (see Figure 1).
    • Fully metal armored, modular structure with a wide range of combination schemes.
    • The cabinet body is made of imported aluminum-zinc coated thin steel plate, processed by machine tools, using advanced multiple folding techniques, connected with pull-riveted nuts and high-strength bolts, ensuring high precision, lightweight, high strength, and strong parts interchangeability.
    • Compatible with VS1-24 series or imported VD4 series vacuum circuit breakers, offering wide applicability, high reliability, and long-term maintenance-free operation.
    • The truck has operational and testing positions, with positioning and display devices at each location, ensuring safety and reliability.
    • Various trucks change according to modular block design, ensuring that trucks of the same specification can be freely interchanged, while trucks of different specifications cannot enter.
    • Grounding switch installation methods: Installed in the middle of the cabinet (front-mounted) to facilitate maintenance from the back of the cabinet with dual-sided access; or installed at the back of the cabinet (rear-mounted) to save space against the wall.
    • Current transformer installation method: Installed in the rear cable room of the cabinet, suspended from the bottom of the large bending plate.
    • The cable room can accommodate up to 9 single-core cables.
    • Each high-voltage chamber is equipped with a pressure relief channel to ensure personnel safety.
    • Highly reliable interlocking device that fully meets the "Five Prevention" safety requirements.
    • The hand truck is transported by a dedicated transport vehicle, making operation easy and flexible.
    • The front and back doors are equipped with observation windows, allowing for easy monitoring of the working status of the internal components.

    External Dimensions of Switchgear

    External Dimensions of Switchgear Diagram

    Product Features

    • Main circuit schematic diagram number, purpose, and single line system diagram, Nominal Voltage, Rated Current, Rated Short-circuit Breaking Current, layout of the distribution room, and arrangement configuration diagram of the switchgear, etc.
    • Requirements for control, measurement, and protection functions of the switchgear, as well as other interlocking and automatic device requirements.
    • Model, specifications, and quantity of the main electrical components inside the switchgear.
    • If bus bridges are needed to connect between switchgear or incoming cabinets, provide specific requirements such as the rated current capacity of the bus bridge, span, height from the ground, etc.
    • If the switchgear is used in special environmental conditions, details should be specified at the time of ordering.
    • Other special requirements.

    Frequently Asked Questions

    Q1: What are the normal operating temperature limits for this switchgear?
    The switchgear is designed to operate in ambient air temperatures with a maximum limit of 40℃ and a minimum limit of -15℃.
    Q2: What is the nominal voltage and rated frequency of the equipment?
    The nominal voltage of this switchgear is 24 kV, and the rated frequency is 50 Hz.
    Q3: Which vacuum circuit breakers are compatible with this switchgear?
    It is fully compatible with the VS1-24 series or imported VD4 series vacuum circuit breakers, ensuring long-term maintenance-free operation.
    Q4: What is the ingress protection (IP) rating of the switch cabinet?
    The outer shell features an IP4X protection rating, while the isolation chamber and circuit breaker room have an IP2X rating when the cabinet door is open.
    Q5: How many cables can the cable room accommodate?
    The spacious cable room design is capable of accommodating up to 9 single-core cables.
    Q6: Can this switchgear be used under conditions exceeding the standard GB3906?
    Yes. If the application environment exceeds the normal conditions specified in GB3906, the specific requirements can be negotiated between the user and the manufacturer.