Leave Your Message

KYN28A-24 Armored Removable AC Metal-Enclosed Switchgear from China Suppliers and Factory for Reliable Power Distribution

,

Overview

,

The KYN28-24 Armored Removable AC Metal-Enclosed Switchgear, a premier product from trusted China suppliers, is expertly designed for three-phase AC power systems operating at 50Hz. This versatile switchgear is ideal for receiving and distributing electrical energy, as well as providing essential control, protection, and monitoring for your circuits.
Manufactured in our state-of-the-art factory, this switchgear adheres to stringent industry standards, including GB3906-2006 3.6-40.5kV AC Metal-Enclosed Switchgear and Controlgear, GB/T11022 Common Technical Requirements for High Voltage Switchgear and Controlgear, IEC62271:200 AC Metal-Enclosed Switchgear and Controlgear for Nominal Voltage above 1kV and below 52kV, and DL/T404 Technical Conditions for Ordering Indoor AC High Voltage Switchgear.

,

    Model and Definitions

    Model and Definitions Diagram

    Application Conditions

    • Ambient Air Temperature: Maximum temperature 40℃, minimum temperature -15℃;
    • Relative Humidity: Daily average not exceeding 95%, daily average vapor pressure not exceeding 2.2 kPa; monthly average not exceeding 90%, monthly average vapor pressure not exceeding 1.8 kPa;
    • Altitude: 1000m and below;
    • Seismic Intensity: Not exceeding 8 degrees;
    • Surrounding air should not be significantly polluted by corrosive or flammable gases, water vapor, etc.;
    • No frequent severe vibration in the area;
    • If used under conditions exceeding the normal environmental conditions specified in GB3906, it should be negotiated between the user and the manufacturer.

    Technical Specifications

    Items Units Data
    Nominal Voltage kV 24
    Rated Frequency Hz 50
    Circuit Breaker Rated Currency A 630 , 1250 , 1600 , 2000 , 2500 , 3150 , 4000
    Switch Cabinet Rated Currency A 630 , 1250 , 1600 , 2000 , 2500 , 3150 , 4000
    Rated Dynamic Stability Current(4s) KA 16 , 20 , 25 , 31.5 , 40 , 50
    Rated Stability Current (Peak) KA 40 , 50 , 63 , 80 , 100 , 125
    Rated Short-circuit Breaking Current KA 16 , 20 , 25 , 31.5 , 40 , 50
    Rated Circuit Making Current (Peak) KA 40 , 50 , 63 , 80 , 100 , 125
    Nominal Insulation Level 1min Power Frequency Withstand Voltage Between Poles, Between Pole and Ground kV 65
    Breakdown Voltage between Poles kV 79
    Lightning lmpulse Withstand Voltage(Peak) Between Poles, Between Pole and Ground kV 125
    Breakdown Voltage Between Poles kV 145
    Level of Protection The shell is lP4X, and the isolation chamber and circuit breaker room are lP2X when the door is open.
    Note: The short-circuit capacity of the current transformer is considered separately.

    Structural Features of Products

    • Structure of the Switchgear (see Figure 1).
    • Fully metal armored, modular structure with a wide range of combination schemes.
    • The cabinet body is made of imported aluminum-zinc coated thin steel plate, processed by machine tools, using advanced multiple folding techniques, connected with pull-riveted nuts and high-strength bolts, ensuring high precision, lightweight, high strength, and strong parts interchangeability.
    • Compatible with VS1-24 series or imported VD4 series vacuum circuit breakers, offering wide applicability, high reliability, and long-term maintenance-free operation.
    • The truck has operational and testing positions, with positioning and display devices at each location, ensuring safety and reliability.
    • Various trucks change according to modular block design, ensuring that trucks of the same specification can be freely interchanged, while trucks of different specifications cannot enter.
    • Grounding switch installation methods: Installed in the middle of the cabinet (front-mounted) to facilitate maintenance from the back of the cabinet with dual-sided access. Installed at the back of the cabinet (rear-mounted) to save space against the wall.
    • Current transformer installation method: Installed in the rear cable room of the cabinet. Suspended from the bottom of the large bending plate.
    • The cable room can accommodate up to 9 single-core cables.
    • Each high-voltage chamber is equipped with a pressure relief channel to ensure personnel safety.
    • Highly reliable interlocking device that fully meets the "Five Prevention" safety requirements.
    • The hand truck is transported by a dedicated transport vehicle, making operation easy and flexible.
    • The front and back doors are equipped with observation windows, allowing for easy monitoring of the working status of the internal components.

    External Dimensions of Switchgear

    External Dimensions of Switchgear Diagram

    Product Features

    • Main circuit schematic diagram number, purpose, and single line system diagram, Nominal Voltage, Rated Current, Rated Short-circuit Breaking Current, layout of the distribution room, and arrangement configuration diagram of the switchgear, etc.
    • Requirements for control, measurement, and protection functions of the switchgear, as well as other interlocking and automatic device requirements.
    • Model, specifications, and quantity of the main electrical components inside the switchgear.
    • If bus bridges are needed to connect between switchgear or incoming cabinets, provide specific requirements such as the rated current capacity of the bus bridge, span, height from the ground, etc.
    • If the switchgear is used in special environmental conditions, details should be specified at the time of ordering.
    • Other special requirements.
    Frequently Asked Questions (FAQ)
    What are the ambient temperature requirements for this switchgear?
    The switchgear is designed to operate under normal ambient air temperatures ranging from a maximum of 40℃ to a minimum of -15℃.
    What is the protection rating (IP level) of the cabinet enclosure?
    The outer shell is rated at IP4X. When the door is open, the isolation chamber and circuit breaker room provide a protection level of IP2X.
    Which vacuum circuit breakers are compatible with this switch cabinet?
    The switchgear is fully compatible with the VS1-24 series as well as imported VD4 series vacuum circuit breakers.
    How does the cabinet design ensure safety during a high-pressure fault?
    Each high-voltage chamber is designed with a dedicated pressure relief channel to protect personnel, combined with a highly reliable interlocking system that meets strict "Five Prevention" safety standards.
    Are the internal hand trucks interchangeable?
    Yes, hand trucks of the same specification are fully interchangeable due to the modular block design. To prevent errors, hand trucks of different specifications are physically blocked from entering.
    What are the installation options for the grounding switch?
    It can be front-mounted (installed in the middle of the cabinet) to allow dual-sided access and maintenance from the back, or rear-mounted (installed at the back) to save space by placing the cabinet against a wall.

    Leave Your Message