HXGN15-12 Box-Type Fixed AC Metal-Enclosed Switchgear - Reliable Power Solution from China Suppliers and Factory
Model and Definitions
Application Conditions
- Altitude: ≤1000m (If there are special requirements, please specify when placing an order. Currently, there are 6 sets operating at an altitude of 5200m.)
- Ambient Temperature: -35℃ to 45℃, with a maximum daily average temperature difference of ≤25℃.
- Relative Humidity: Daily relative humidity should not exceed 95%, and monthly average relative humidity should not exceed 90%.
- Seismic Resistance: 8 degrees
- Operation Environment: It should be used in areas without severe vibrations and shocks, and where there is no risk of fire, chemical corrosion, or explosion.
Standards
- GB3906-2006: "AC Metal-Enclosed Switchgear and Controlgear for 3.6 kV to 40.5 kV"
- IEC 60298-1990: "AC Metal-Enclosed Switchgear and Controlgear for Nominal Voltage Above 1kV and Below 52kV"
- GB/T11022-2011: "Common Technical Requirements for High-Voltage Switchgear and Controlgear Standards"
Technical Parameters
| No. | Items | Units | Value |
| 1 | Nominal Voltage | KV | 12 |
| 2 | Rated Frequency | Hz | 50 |
| 3 | Main Bus Rated Current/Maximum Rated Current of Fuse | A | 630, 125 |
| 4 | Main Circuit, Ground Circuit Rated Short-Time Withstand Current | KA/S | 20, 3 |
| 5 | Main Circuit, Ground Circuit Rated Peak Withstand Current of Main | KA | 50 |
| 6 | Rated Short-Circuit Closing Current of Main Circuit and Ground Circuit | KA | 50 |
| 7 | Full Capacity Breaking Number of Load Switch | Time | 100 |
| 8 | Breaking Current of Fuse | KA | 31.5, 40 |
| 9 | Rated Closed Loop Breaking Current | A | 630 |
| 10 | Rated Transfer Current | A | 1600 |
| 11 | Machinery Service Life | Time | 2000 |
| 12 | 1 Minute Power Frequency Withstand Voltage (Peak Value) Relative to Ground/Isolation Break | KV | 42, 48 |
| 13 | Lightning Impulse Withstand Voltage (Peak Value) Phase-to-Phase, Relative to Ground/Isolation Break | KV | 75, 85 |
| 14 | 1 Minute Power Frequency Withstand Voltage of Time Circuit | KV | 2 |
| 15 | Level of Protection | IP3X |
Dimensions
| Dimension Type | Value (mm) | Scope of Application |
| Height H | 1400 | Suitable for Single-core Electric Cable |
| 1600 | Suitable for Single-core Electric Cable | |
| 1800 | Suitable for Three-core Electric Cable | |
| Width W | 375 | Incoming Line & Outcoming Line |
| 500 | - | |
| 750 | - | |
| Depth D | 918 | - |
Structural Brief
Frequently Asked Questions
Q1: Can this switchgear be used at high altitudes?
Yes. While the standard design is rated for altitudes ≤1000m, it can be customized for higher altitudes. Currently, there are 6 sets successfully operating at an altitude of 5200m.
Q2: What is the operating temperature range for this equipment?
The switchgear is designed to operate reliably in ambient temperatures ranging from -35℃ to 45℃, with a maximum daily average temperature difference of ≤25℃.
Q3: Which international and national standards does this product comply with?
The equipment complies with GB3906-2006 (for 3.6 kV to 40.5 kV AC metal-enclosed switchgear), IEC 60298-1990 (for nominal voltages above 1kV and below 52kV), and GB/T11022-2011 (common technical requirements for high-voltage switchgear).
Q4: What is the IP protection level of the switchgear?
This switchgear has a protection rating of IP3X, which ensures standard protection against solid foreign objects.
Q5: How do I choose the right height dimension for my cables?
The height (H) of the switchgear depends on your cable type: heights of 1400mm and 1600mm are suitable for single-core electric cables, while a height of 1800mm is designed for three-core electric cables.