01
GZDW DC Power Cabinet
Model and Definitions

Application Conditions
◇ Altitude: no more than 2000m.
◇ Ambient temperature: -5℃~+40℃.
◇ Relative Humidity: not more than 90%. (at 20+5℃)
Note: Special conditions can be negotiated with our company
Technical Reference
◇ Input Power Voltage: Three-phase AC 380V+10%, 50Hz5% ;
◇ Output DC voltage rating: 24v; 48v; 110v; 220v;
◇ Output DC current rating: 5A, 8A, 10A, 15A, 20A, 30A, 40A, 50A, 80A, 100A, 150A, 200A, 250A .
◇ Battery Rated Capacity: 10Ah, 20Ah, 38Ah, 40Ah, 50Ah, 60Ah, 65Ah, 80Ah, 100Ah, 150Ah, 200Ah, 250Ah, 300Ah, 400Ah.
◇ Voltage adjustment range (see table below)
◇ Output DC current adjustment range: 0~100% of rated value
◇ Stable accuracy <±1%
◇ Steady current accuracy <±1%
◇ Ripple coefficient: <1%
◇ Machine noise: <55dB
◇ Main transformer temperature rise: 70℃
◇ Working mode: continuous working
◇ Efficiency>90%
◇ Level of Protection: IP20~IP30
Output DC voltage rating | 24V | 48V | 110V | 220V |
Float charge voltage adjustment range | 21-28 | 43-57 | 99-130 | 198-260 |
Equalizing charging voltage adjustment range | 27-31 | 54-62 | 125-140 | 198-286 |
Main charging voltage adjustment range | 21-36 | 43-70 | 99-162 | 187-310 |
Product appearance and installation dimensions