GTXGN-12 AC Metal Solid Insulated Ring Main Unit - Reliable Power Distribution Solution from China Suppliers and Factory
| No. | Units | Parameters | |||
|---|---|---|---|---|---|
| Nominal Voltage | KV | 12 | |||
| Rated Frequency | Hz | 50 | |||
| Rated Currency | A | 630 | 1250 | ||
| Nominal Insulation Level | Power Frequency Withstand Voltage | Break Point | KV | 48 | |
| Phase-to-Phase | KV | 42 | |||
| Relative | KV | 42 | |||
| Lighting Impulse Withstand Voltage | Break Point | KV | 85 | ||
| Phase-to-Phase | KV | 75 | |||
| Relative | KV | 75 | |||
| Rated Short-circuit Breaking Current(1s) | KA | 25 | 31.5 | ||
| Rated Short-time Withstand Current(4s) | KA | 25 | 31.5 | ||
| Rated Peak Withstand Current(lp) | KA | 36 | 80 | ||
| Rated Circuit Making Current(Peak)(1ma) | KA | 36 | 80 | ||
| Level of Protection for Shell | - | IP4X | |||
| Operation Mode | - | Spring-operated | |||
| No. | Items | Units | Parameters | ||
|---|---|---|---|---|---|
| 1 | Nominal Voltage | kV | 12 | ||
| 2 | Rated Currency | A | 630 | 1250 | |
| 3 | 4S Rated Short-time Withstand Current (Valid Value) | kA | 25 | 31.5 | |
| 4 | Rated Peak Withstand Current (Peak) | kA | 63 | 80 | |
| 5 | 1min Power Frequency Withstand Voltage | Phase-to-Phase and Ground | kV | 42 | |
| Isolation Break Point | 48 | ||||
| 6 | Rated Lighting Impulse Withstand Voltage | Phase-to-Phase and Ground | kV | 75 | |
| Isolation Break Point | 85 | ||||
| 7 | Main Switch Machinery Service Life | Time | 3000 | ||
| 8 | Ground Switch Machinery Service Life | Time | 3000 | ||
Isolation Knife Visible Break Point
The cabinet features a prominent visible window for the Isolation Break Point, allowing personnel to observe the three working positions: isolation engaged, isolation disengaged, and grounding engaged. This design facilitates the on-site staff in determining the position of the isolation knife, ensuring a high level of safety.
Internal Arc Design
Internal Arc Pressure Valve: When an arc occurs inside the product, the pressure will be released through this valve, directing the arc away into the cable trench to prevent accidental injury to operators.
Green and Environmentally Friendly
Designed with environmentally friendly materials, this product does not use SF6 gas as an arc extinguishing medium or insulation, thus avoiding environmental pollution. The one-time circuit design minimizes contact points, ensuring low energy consumption during operation.
| Model | Width (mm) | Depth (mm) | Height (mm) |
|---|---|---|---|
| Load Switch PT Cabinet (CPT) | 500 | 950 | 1650 |
| Circuit Breaker Cabinet (VB) | 400 | 950 | 1650 |
| Circuit Breaker Cabinet(V) | 400 | 950 | 1650 |
| Circuit Breaker Bus Coupling Cabinet (VZ) | 400 | 950 | 1650 |
| Busbar Lifting Cabinet(G) | 400 | 950 | 1650 |
| Load Switch Fuse Combination Cabinet (F) | 500 | 950 | 1650 |