0102030405
Environmentally-Friendly Gas-Insulated Metal-Enclosed Switchgear - China Suppliers & Factory Solutions
Model and Definitions
Normal Use Environmental Conditions
Maximum Temperature: +40℃
Minimum Temperature: -25℃
24-Hour Average Temp: ≤35℃
Max Average Relative Humidity: 24-Hour Average ≤95%, Monthly Average ≤90%
Altitude: ≤1500 meters (standard gas pressure); special instructions required for >1500 meters
Special Conditions: Prior consultation recommended for environments beyond normal specifications.
Major Technical Parameters
| Units | Items | C Module | F Module | V Module | |
|---|---|---|---|---|---|
| Load Switch | Composite Apparatus | Vacuum Breaker | Isolation/ Earthing Switch | ||
| 1 | Nominal Voltage kV | 12 | |||
| 2 | 1min Power Frequency Withstand Voltage kV | 42/48 | |||
| 3 | Lightning Impulse Withstand Voltage kV | 75/85 | |||
| 4 | Rated Current A | 630 | 630 | 630 | |
| 5 | Breaking Capacity | ||||
| Closed Loop Breaking Current (A) | 630 | ||||
| Cable Charging Breaking Current (A) | 135 | ||||
| 5% Active Load Breaking Current (A) | 31.5 | ||||
| Ground Fault Breaking Current (A) | 200 | ||||
| Short-Circuit Breaking Current (kA) | 31.5* | 25 | |||
| 6 | Rated Transfer Current A | 1500 | |||
| 7 | Maximum Current Near Circuit Breaker (A) | 125 | |||
| 8 | Short-Circuit Closing Current (kA) | 63 | 80* | 25 | |
| 9 | Short-Time Withstand Current (kA) | 25 | 25 | 25 | |
| 10 | Short-Circuit Duration (s) | 4 | 4 | 4 | |
| 11 | Machinery Service Life Time | 5000 | 5000 | 10000 | 3000 |
| 12 | Gas Pressure (MPa) | 0.025 (20°C) | |||
| 13 | Annual Leakage Rate | ≤0.05% | |||
| 14 | Arc Extinguishing Method | Vacuum Extinction | |||
| 15 | Level of Protection | IP67/3X (Gas Tank/Shell) | |||
External Dimensions
| Dimension | 1-way | 2-way | 3-way | 4-way | 5-way |
|---|---|---|---|---|---|
| W (mm) | 371 | 696 | 1021 | 1346 | 1671 |
| H (mm) | 1336 | ||||
| D (mm) | 850 (total 935) | ||||
Outdoor Open and Close Solution
Frequently Asked Questions
Q1: What are the normal operating temperature limits for this equipment?
The equipment is designed to operate in environmental temperatures ranging from a minimum of -25℃ to a maximum of +40℃, with a 24-hour average temperature not exceeding 35℃.
Q2: Can the system be used at altitudes higher than 1500 meters?
The standard type is rated for altitudes up to 1500 meters under standard gas pressure. For installations exceeding 1500 meters, special instructions and custom consultations are required.
Q3: What is the protection level and annual gas leakage rate?
The gas tank features an IP67 protection rating, while the shell holds an IP3X rating. The annual gas leakage rate is exceptionally low at ≤0.05%.
Q4: How does the mechanical service life differ between modules?
The mechanical service life varies by module: the V Module (Vacuum Breaker) has a life of 10,000 operations, the C Module (Load Switch) and F Module (Composite Apparatus) support 5,000 operations, and the Isolation/Earthing Switch supports 3,000 operations.
Q5: What are the dimensions for different loop configurations?
While the height is 1336 mm and depth is 850 mm (935 mm total) across all configurations, the width (W) scales as follows: 1-way: 371mm, 2-way: 696mm, 3-way: 1021mm, 4-way: 1346mm, and 5-way: 1671mm.
Q6: What arc extinguishing technology is used in the switchgear?
This switchgear utilizes the reliable Vacuum Extinction method for high-efficiency and safe arc extinguishing during operations.