0102030405
Environmentally-Friendly Gas-Insulated Metal-Enclosed Switchgear Air-12/T630-25 - China Suppliers and Factory
Model and Definitions
Normal Use Environmental Conditions
◇
Maximum Temperature: +40℃
◇
Minimum Temperature: -25℃
◇
24-Hour Average Temperature: ≤35℃
◇
Maximum Average Relative Humidity: 24-Hour Average ≤95%, Monthly Average: ≤90%
◇
Altitude: ≤1500 meters (for standard type, under standard gas pressure); special instructions required for >1500 meters
◇
For special operating conditions beyond normal use environment, prior consultation with our company is recommended.
Major Technical Parameters
| Units | Items | C Module | F Module | V Module | |
| Load Switch | Composite Apparatus | Vacuum Breaker | Isolation/ Earthing Switch | ||
| 1 | Nominal Voltage kV | 12 | |||
| 2 | 1min Power Frequency Withstand Voltage kV | 42/48 | |||
| 3 | Lighting Impulse Withstand Voltage kV | 75/85 | |||
| 4 | Rated Current A | 630 | 630 | 630 | |
| 5 | Breaking Capacity | ||||
| Closed Loop Breaking Current (A) | 630 | ||||
| Cable Charging Breaking Current (A) | 135 | ||||
| 5% Active Load Breaking Current (A) | 31.5 | ||||
| Ground Fault Breaking Current (A) | 200 | ||||
| Short-Circuit Breaking Current (kA) | 31.5* | 25 | |||
| 6 | Rated Transfer Current A | 1500 | |||
| 7 | Maximum Current Near Circuit Breaker (A) | 125 | |||
| 8 | Short-Circuit Closing Current (kA) | 63 | 80* | 25 | |
| 9 | Short-Time Withstand Current (kA) | 25 | 25 | 25 | |
| 10 | Short-Circuit Duration (s) | 4 | 4 | 4 | |
| 11 | Machinery Service Life Time | 5000 | 5000 | 10000 | 3000 |
| 12 | Gas Pressure (MPa) | 0.025 (20°C) | |||
| 13 | Annual Leakage Rate | ≤0.05% | |||
| 14 | Arc Extinguishing Method | Vacuum Extinction | |||
| 15 | Level of Protection | IP67/3X (Gas Tank/Shell) | |||
External Dimensions
| 1-way | 2-way | 3-way | 4-way | 5-way | |
| W (mm) | 371 | 696 | 1021 | 1346 | 1671 |
| H (mm) | 1336 | ||||
| D (mm) | 850 (total 935) | ||||
Outdoor Open and Close Solution
Frequently Asked Questions (FAQ)
What are the environmental temperature limits for normal equipment operation?
The equipment operates reliably within a maximum temperature of +40℃ and a minimum temperature of -25℃, with a 24-hour average temperature not exceeding 35℃.
Is this equipment suitable for installations at high altitudes?
Yes. The standard type is designed for altitudes up to 1500 meters under standard gas pressure. For installations exceeding 1500 meters, special instructions and consultation are required.
What is the protection rating (IP code) of the gas tank and shell?
The gas tank features an IP67 protection level, while the external shell is rated at IP3X, ensuring robust protection against ingress.
What is the gas leakage rate and arc extinguishing mechanism of this model?
The annual gas leakage rate is exceptionally low at ≤0.05%, and it utilizes the Vacuum Extinction method for highly efficient arc suppression.
What are the physical dimensions (width, height, depth) for different module configurations?
The height is 1336 mm and the depth is 850 mm (total 935 mm). The width (W) varies by configuration: 371 mm (1-way), 696 mm (2-way), 1021 mm (3-way), 1346 mm (4-way), and 1671 mm (5-way).