Leave Your Message

Eco-Friendly Gas-Insulated Switchgear Air-12/T630-25 by China Suppliers & Factory for Smart Distribution Solutions

,

Overview

,

The Air-12 Environmentally-Friendly Gas-Insulated Metal-Enclosed Switchgear stands out as a leading solution in the power distribution sector. This innovative switchgear employs a vacuum arc-extinguishing chamber and utilizes eco-friendly gas as its primary insulating medium, supported by minimal solid insulation. Operating at zero gauge pressure or slightly positive pressure (gas pressure in the tank ≤ 0.02 MPa), it eliminates encapsulation in the main circuit while maintaining exceptional insulation capabilities between phases and to ground, in accordance with air insulation standards for distribution switchgear.

,

As one of the most sought-after three-phase AC intelligent gas-insulated cabinets, this product is extensively used in complete switchgear systems across various sectors. With rapid urbanization and an expanding power market in China, the demand for environmentally friendly gas-insulated switchgear is on the rise, revealing significant market potential for suppliers and factories alike.

,

In addition to its robust features, the Air-12 switchgear integrates advanced functionalities, including data collection, processing, storage, online monitoring, and analytical capabilities. This ensures intelligent remote management of the distribution network, promoting a safe, reliable, and efficient power system. The switchgear is designed to meet contemporary demands for grid optimization, electrical safety, energy management, and conservation.

,

Ideal for application in intelligent distribution fields such as transportation, manufacturing, healthcare, education, commercial buildings, and residential complexes, this environmentally-friendly solution sets the standard for future energy-efficient innovations.

,

    Model and Definitions

    Model and Definitions Diagram

    Normal Use Environmental Conditions

    Maximum Temperature: +40℃
    Minimum Temperature: -25℃
    24-Hour Average Temperature: ≤35℃
    Maximum Average Relative Humidity: 24-Hour Average ≤95%, Monthly Average: ≤90%
    Altitude: ≤1500 meters (for standard type, under standard gas pressure); special instructions required for >1500 meters
    For special operating conditions beyond normal use environment, prior consultation with our company is recommended.

    Major Technical Parameters

    Units Items C Module F Module V Module
    Load Switch Composite Apparatus Vacuum Breaker Isolation/Earthing Switch
    1 Nominal Voltage kV 12
    2 1min Power Frequency Withstand Voltage kV 42/48
    3 Lighting Impulse Withstand Voltage kV 75/85
    4 Rated Currency A 630 - 630 630
    5 Breaking Capacity - - - -
    Closed Loop Breaking Current (A) 630 - - -
    Cable Charging Breaking Current (A) 135 - - -
    5% Active Load Breaking Current (A) 31.5 - - -
    Ground Fault Breaking Current (A) 200 - - -
    Short-Circuit Breaking Current (kA) - 31.5* 25 -
    6 Rated Transfer Current A - 1500 - -
    7 Maximum Current Near Circuit Breaker (A) - 125 - -
    8 Short-Circuit Closing Current (kA) 63 80* 25 -
    9 Short-Time Withstand Current (kA) 25 - 25 25
    10 Short-Circuit Duration (s) 4 - 4 4
    11 Machinery Service Life Time 5000 5000 10000 3000
    12 Gas Pressure (MPa) 0.025 (20°C)
    13 Annual Leakage Rate ≤0.05%
    14 Arc Extinguishing Method Vacuum Extinction
    15 Level of Protection IP67/3X (Gas Tank/Shell)

    External Dimensions

    External Dimensions Drawing
    Dimensions 1-way 2-way 3-way 4-way 5-way
    W (mm) 371 696 1021 1346 1671
    H (mm) 1336
    D (mm) 850 (total 935)

    Outdoor Open and Close Solution

    Outdoor Open and Close Solution Diagram

    Frequently Asked Questions

    Q: What is the normal operating temperature range for the equipment?
    A: The equipment is designed to operate within a maximum temperature of +40℃ and a minimum temperature of -25℃, with a 24-hour average temperature not exceeding 35℃.
    Q: Can this equipment be installed at altitudes higher than 1500 meters?
    A: The standard type is rated for altitudes ≤1500 meters under standard gas pressure. For installations exceeding 1500 meters, special instructions and prior consultation are required.
    Q: What is the protection level of the gas tank and the outer shell?
    A: The protection level is IP67 for the Gas Tank and IP3X for the Shell, ensuring high reliability and environmental resistance.
    Q: What is the mechanical service life of the different switch modules?
    A: The machinery service life is 5,000 operations for the C Module (Load Switch) and F Module (Composite Apparatus), 10,000 operations for the V Module (Vacuum Breaker), and 3,000 operations for the Isolation/Earthing Switch.
    Q: What are the overall width measurements for the different way configurations?
    A: The widths are: 371 mm for 1-way, 696 mm for 2-way, 1021 mm for 3-way, 1346 mm for 4-way, and 1671 mm for 5-way configurations. The height is standard at 1336 mm, and the depth is 850 mm (total 935 mm).
    Q: What is the annual gas leakage rate and arc extinguishing method?
    A: The equipment features an annual leakage rate of ≤0.05% and utilizes Vacuum Extinction as its primary arc extinguishing method.