Leave Your Message

DFW Switched Cable Branch Box - Reliable China Factory Suppliers for Compact Power Distribution Solutions

,

Functional Characteristics

,

Our product features prefabricated, touchable silicone rubber cable terminals that are fully sealed, fully insulated, and maintenance-free, ensuring reliable personal safety. The compact structure is not only small and aesthetically pleasing but also built with a double-layer stainless steel body designed to last over twenty years. This product facilitates regional power outage maintenance without interrupting the operation of the main network, thereby minimizing the extent of power outages. It is compatible with one or multiple SF6 Load Switches, offering a flexible and diverse wiring method, including branch outgoing lines accommodating up to 8 circuits. Additionally, optional components such as surge protectors, short-circuit fault indicators, and current-limiting fuses are available to cater to various user needs. As a leading China supplier and factory, we are committed to providing high-quality solutions that meet the specific demands of our customers.

,

    Model and Definitions

    Model and Definitions Diagram

    DFW Technical Parameters

    No. Items Parameters
    1 Nominal Voltage 12kV
    2 Rated Currency 630A
    3 Power Frequency Withstand Voltage (Phase to Ground) 42kV/min
    4 Lightning lmpulse Voltage 75kV
    5 Rated Breaking Current 630A
    6 Rated Short-circuit Making Current(Peak Value) 50kA
    7 Rated Short-time Withstand Current 25kA/4S
    8 Rated Peak Withstand Current 50kA
    9 Rated Peak Withstand Current 45A
    10 Rated Breaking Capacitive Current 16A
    11 Full Load Breaking Time >100
    12 Mechanical Operation Time for Opening and Closing 2000

    External Schematic Diagram

    External Schematic Diagram

    Basic Structure

    Basic Structure Detail 1
    Basic Structure Detail 2

    Technical Requirements

    • The inner side of the brick wall is to be sealed with a 1:3 cement mortar mix and treated for waterproofing.
    • Beam penetrations should use φ6 concrete operations.
    • The foundation channel steel must undergo anti-corrosion treatment after fabrication.
    • After the installation of the branch box is completed, the area around the base should be sealed with cement.
    • Waterproof measures must be taken at the manhole entrance.
    • Grounding electrodes should be pre-embedded in the foundation, with grounding resistance meeting the requirements set by the power department.

    Ordering Instructions

    • The product model and any special requirements from the user can provide a one-time diagram.
    • The standard cross-sections for incoming and outgoing lines and branch cables.
    • The quantity of optional surge protectors and short-circuit fault indicators.

    Frequently Asked Questions (FAQ)

    What is the nominal voltage and rated current of the DFW?

    The DFW features a nominal voltage of 12kV and a rated current of 630A.

    What are the foundation anti-corrosion requirements?

    The foundation channel steel must undergo proper anti-corrosion treatment after fabrication.

    What is the mechanical operation life of the DFW switch?

    The mechanical operation time for opening and closing is rated at 2000 cycles.

    What details are needed when placing an order?

    You should specify the product model, standard cross-sections for incoming/outgoing lines and branch cables, and the required quantity of optional surge protectors and short-circuit fault indicators.

    What waterproofing measures must be taken during installation?

    The inner side of the brick wall must be sealed with a 1:3 cement mortar mix and waterproofed, and waterproof measures must be taken at the manhole entrance.

    What is the lightning impulse voltage rating for this equipment?

    The rated lightning impulse voltage parameter for the DFW is 75kV.