China ZGS11-12 Combined American Prefabricated Substation - Reliable Suppliers & Factory for 10kV Solutions
Model meaning
Conditions of Use
- Altitude not exceeding 1000m;
- Ambient temperature: -35℃~+40℃;
- Relative humidity: daily average value is not more than 95%, monthly average value is not more than 90%;
- Installation location: A well-ventilated place without fire or explosion hazards, chemical corrosive gases, and a ground inclination of no more than 3 °.
Technical Parameters
| NO. | Name | Unit | Technical Parameters |
|---|---|---|---|
| 1 | Rated voltage | KV | 10/0.4(high pressure/1 low pressure) |
| 2 | Maximum operating voltage | KV | 12 (high voltage side |
| 3 | Rated frequency | HZ | 50 |
| 4 | Rated capacity | KVA | 50-1600 |
| 5 | 1 minute power frequency withstand voltage | KV | 35 |
| 6 | Lightning impulse voltage | KV | 75 |
| 7 | Cooling method | - | Oil-immersed self-cooling |
| 8 | High voltage backup fuse breaking current | KA | 50 |
| 9 | Plug-in fuse breaking current | KA | 25 |
| 10 | Ambient temperature | - | -35~+40 |
| 11 | Coil allowable temperature rise | ℃ | 65 |
| 12 | No-load voltage regulation | ℃ | ±5%or±2×2.5% |
| 13 | Noise Level | db | 50 |
| 14 | Protection level | - | lp43 |
Installation Dimensions
Ordering Instructions
- Product operation location and special requirements;
- Provide product ordering drawings, which should include wiring diagrams, and should indicate transformer capacity, main component models and specifications, power distribution branch circuits and capacity;
- When electric energy metering and reactive power automatic compensation devices are required, the configuration requirements of the metering electric energy meter and mutual inductor shall be provided, and the capacity of the compensation capacitor shall be indicated;
- Indicate the requirements for product surface treatment;
- When ordering combined transformers, please specify terminal type or ring network type.
Examples of some product appearance drawings
Frequently Asked Questions (FAQ)
What is the standard ambient temperature range for operating this transformer?
The transformer is designed to operate reliably within an ambient temperature range of -35℃ to +40℃.
What is the maximum installation altitude limit for this equipment?
The standard installation altitude for this transformer should not exceed 1000 meters above sea level.
What key drawings and specifications are required when placing an order?
Customers must provide product ordering drawings, including detailed wiring diagrams, indicating transformer capacity, main component models and specifications, as well as power distribution branch circuits and capacity.
What cooling method and protection rating does this model feature?
The transformer utilizes oil-immersed self-cooling technology and features an IP43 protection level.
What are the environmental requirements regarding fire hazards and ground inclination?
The installation site must be well-ventilated, free from fire or explosion hazards, and without chemical corrosive gases. Additionally, the ground inclination of the installation spot must not exceed 3 degrees.