0102030405
China Suppliers Factory SCB-RL Triangular Three-Dimensional Wound Core Dry-Type Power Transformer for High-Rise Applications
Model meaning
| Rated capacity (KVA) | Voltage combination | Connection Group Label | No load Power consumption (W) | Load loss group A (W) | No load Current(%) | Short circuit impedance (%) | Sound Power class dB(A) | Dimensions (mm (length, width and height) Installation 4φ18 | Total weight (kg) | ||||
| high pressure (KV) | Demarcation range | Low pressure | 100°C | 100°C | 100°C | ||||||||
| B(100°C) | F(120°C) | H(145°C) | |||||||||||
| 30 | 6 6.3 6.6 10 10.5 11 |
±5 or ±2 ×2.5 |
0.4 | Dyn11 | 190 | 670 | 710 | 760 | 2.4 | 4.0 | 35 | 900x900x800 | 300 |
| 50 | 270 | 940 | 1000 | 1070 | 2.4 | 955x900x900 | 350 | ||||||
| 80 | 370 | 1290 | 1380 | 1480 | 1.8 | 36 | 985x950x960 | 400 | |||||
| 100 | 400 | 1480 | 1570 | 1690 | 1.8 | 1035x1250x980 | 450 | ||||||
| 125 | 470 | 1740 | 1850 | 1980 | 1.6 | 37 | 1060x1280x1000 | 500 | |||||
| 160 | 540 | 2000 | 2130 | 2280 | 1.6 | 1120x1320x1050 | 680 | ||||||
| 200 | 620 | 2370 | 2530 | 2710 | 1.4 | 38 | 1130x1330x1015 | 770 | |||||
| 250 | 720 | 2590 | 2760 | 2960 | 1.4 | 1170x1330x1165 | 900 | ||||||
| 315 | 880 | 3270 | 3470 | 3730 | 1.2 | 39 | 1185x1360x1225 | 1010 | |||||
| 400 | 980 | 3750 | 3990 | 4280 | 1.2 | 1210x1380x1300 | 1205 | ||||||
| 500 | 1160 | 4590 | 4880 | 5230 | 1.2 | 40 | 1245x1400x1380 | 1400 | |||||
| 630 | 1340 | 5530 | 5880 | 6290 | 1 | 6.0 | 41 | 1295x1410x1355 | 1515 | ||||
| 630 | 1300 | 5610 | 5960 | 6400 | 1 | 1295x1410x1355 | 1515 | ||||||
| 800 | 1520 | 6550 | 6960 | 7460 | 1 | 42 | 1375x1450x1480 | 1830 | |||||
| 1000 | 1770 | 7650 | 8130 | 8760 | 1 | 1430x1480x1525 | 2170 | ||||||
| 1250 | 2090 | 9100 | 9690 | 10370 | 1 | 43 | 1480x1500x1570 | 2525 | |||||
| 1600 | 2450 | 11050 | 11730 | 12580 | 1 | 44 | 1500x1520x1710 | 2930 | |||||
| 2000 | 3050 | 13600 | 14450 | 15560 | 0.8 | 45 | 1570x1550x1735 | 3430 | |||||
| 2500 | 3600 | 16150 | 17170 | 18450 | 0.8 | 46 | 1625x1600x1825 | 4030 | |||||
| 1600 | 2450 | 12280 | 12960 | 13900 | 1 | 8.0 | 44 | 1500x1520x1710 | 2930 | ||||
| 2000 | 3050 | 15020 | 15960 | 17110 | 0.8 | 45 | 1570x1550x1735 | 3430 | |||||
| 2500 | 3600 | 17760 | 18890 | 20290 | 0.8 | 46 | 1625x1610x1825 | 4080 | |||||
ℹ
Note: Due to the continuous updating of products, the dimensions and weight of the products in the table may change. Please refer to the dimensions provided when ordering.
SCB11-RL-(30-2500)/11Three-dimensional triangle core dry-type power transformer
| Rated capacity (KVA) | Voltage combination | Connection Group Label | No load Power consumption (W) | Load loss group A (W) | No load Current(%) | Short circuit impedance (%) | Sound Power class dB(A) | Dimensions (mm (length, width and height) Installation 4φ18 | Total weight (kg) | ||||
| high pressure (KV) | Demarcation range | Low pressure | 100°C | 100°C | 100°C | ||||||||
| B(100°C) | F(120°C) | H(145°C) | |||||||||||
| 30 | 6 6.3 6.6 10 10.5 11 |
±5 or ±2 ×2.5 |
0.4 | Dyn11 | 670 | 710 | 760 | 2.4 | 4.0 | 35 | 900x900x800 | 300 | |
| 50 | 940 | 1000 | 1070 | 2.4 | 955x900x900 | 350 | |||||||
| 80 | 1290 | 1380 | 1480 | 1.8 | 36 | 985x950x960 | 400 | ||||||
| 100 | 1480 | 1570 | 1690 | 1.8 | 1035x1250x980 | 450 | |||||||
| 125 | 1740 | 1850 | 1980 | 1.6 | 37 | 1060x1280x1000 | 500 | ||||||
| 160 | 2000 | 2130 | 2280 | 1.6 | 1120x1320x1050 | 680 | |||||||
| 200 | 2370 | 2530 | 2710 | 1.4 | 38 | 1130x1330x1015 | 770 | ||||||
| 250 | 2590 | 2760 | 2960 | 1.4 | 1170x1330x1165 | 900 | |||||||
| 315 | 3270 | 3470 | 3730 | 1.2 | 39 | 1185x1360x1225 | 1010 | ||||||
| 400 | 3750 | 3990 | 4280 | 1.2 | 1210x1380x1300 | 1205 | |||||||
| 500 | 4590 | 4880 | 5230 | 1.2 | 40 | 1245x1400x1380 | 1400 | ||||||
| 630 | 5530 | 5880 | 6290 | 1 | 6.0 | 41 | 1295x1410x1355 | 1515 | |||||
| 630 | 5610 | 5960 | 6400 | 1 | 1295x1410x1355 | 1515 | |||||||
| 800 | 6550 | 6960 | 7460 | 1 | 42 | 1375x1450x1480 | 1830 | ||||||
| 1000 | 7650 | 8130 | 8760 | 1 | 1430x1480x1525 | 2170 | |||||||
| 1250 | 9100 | 9690 | 10370 | 1 | 43 | 1480x1500x1570 | 2525 | ||||||
| 1600 | 11050 | 11730 | 12580 | 1 | 44 | 1500x1520x1710 | 2930 | ||||||
| 2000 | 13600 | 14450 | 15560 | 0.8 | 45 | 1570x1550x1735 | 3430 | ||||||
| 2500 | 16150 | 17170 | 18450 | 0.8 | 46 | 1625x1600x1825 | 4030 | ||||||
| 1600 | 12280 | 12960 | 13900 | 1 | 8.0 | 44 | 1500x1520x1710 | 2930 | |||||
| 2000 | 15020 | 15960 | 17110 | 0.8 | 45 | 1570x1550x1735 | 3430 | ||||||
| 2500 | 17760 | 18890 | 20290 | 0.8 | 46 | 1625x1610x1825 | 4080 | ||||||
ℹ
Note: Due to the continuous updating of products, the dimensions and weight of the products in the table may change. Please refer to the dimensions provided when ordering.
SCB13-RL-(30-2500)/13Three-dimensional triangle core dry-type power transformer
| Rated capacity (KVA) | Voltage combination | Connection Group Label | No load Power consumption (W) | Load loss group A (W) | No load Current(%) | Short circuit impedance (%) | Sound Power class dB(A) | Dimensions (mm (length, width and height) Installation 4φ18 | Total weight (kg) | ||||
| high pressure (KV) | Demarcation range | Low pressure | 100°C | 100°C | 100°C | ||||||||
| B(100°C) | F(120°C) | H(145°C) | |||||||||||
| 30 | 6 6.3 6.6 10 10.5 11 |
±5 or ±2 ×2.5 |
0.4 | Dyn11 | 670 | 710 | 760 | 2.4 | 4.0 | 35 | 900x900x800 | 300 | |
| 50 | 940 | 1000 | 1070 | 2.4 | 955x900x900 | 350 | |||||||
| 80 | 1290 | 1380 | 1480 | 1.8 | 36 | 985x950x960 | 400 | ||||||
| 100 | 1480 | 1570 | 1690 | 1.8 | 1035x1250x980 | 450 | |||||||
| 125 | 1740 | 1850 | 1980 | 1.6 | 37 | 1060x1280x1000 | 500 | ||||||
| 160 | 2000 | 2130 | 2280 | 1.6 | 1120x1320x1050 | 680 | |||||||
| 200 | 2370 | 2530 | 2710 | 1.4 | 38 | 1130x1330x1015 | 770 | ||||||
| 250 | 2590 | 2760 | 2960 | 1.4 | 1170x1330x1165 | 900 | |||||||
| 315 | 3270 | 3470 | 3730 | 1.2 | 39 | 1185x1360x1225 | 1010 | ||||||
| 400 | 3750 | 3990 | 4280 | 1.2 | 1210x1380x1300 | 1205 | |||||||
| 500 | 4590 | 4880 | 5230 | 1.2 | 40 | 1245x1400x1380 | 1400 | ||||||
| 630 | 5530 | 5880 | 6290 | 1 | 6.0 | 41 | 1295x1410x1355 | 1515 | |||||
| 630 | 5610 | 5960 | 6400 | 1 | 1295x1410x1355 | 1515 | |||||||
| 800 | 6550 | 6960 | 7460 | 1 | 42 | 1375x1450x1480 | 1830 | ||||||
| 1000 | 7650 | 8130 | 8760 | 1 | 1430x1480x1525 | 2170 | |||||||
| 1250 | 9100 | 9690 | 10370 | 1 | 43 | 1480x1500x1570 | 2525 | ||||||
| 1600 | 11050 | 11730 | 12580 | 1 | 44 | 1500x1520x1710 | 2930 | ||||||
| 2000 | 13600 | 14450 | 15560 | 0.8 | 45 | 1570x1550x1735 | 3430 | ||||||
| 2500 | 16150 | 17170 | 18450 | 0.8 | 46 | 1625x1600x1825 | 4030 | ||||||
| 1600 | 12280 | 12960 | 13900 | 1 | 8.0 | 44 | 1500x1520x1710 | 2930 | |||||
| 2000 | 15020 | 15960 | 17110 | 0.8 | 45 | 1570x1550x1735 | 3430 | ||||||
| 2500 | 17760 | 18890 | 20290 | 0.8 | 46 | 1625x1610x1825 | 4080 | ||||||
ℹ
Note: Due to the continuous updating of products, the dimensions and weight of the products in the table may change. Please refer to the dimensions provided when ordering.
Frequently Asked Questions (FAQ)
What is a three-dimensional triangle core dry-type power transformer?
It is an advanced dry-type power transformer featuring a wound core design where the three core limbs are arranged in a symmetrical, three-dimensional triangular structure. This configuration balances the three-phase magnetic circuit, reduces no-load losses, and significantly lowers noise levels.
What are the main differences between SCB11 and SCB13 series transformers?
The primary difference lies in efficiency and energy savings. The SCB13 series has a more optimized core structure and material design, which results in lower no-load power consumption and reduced operating losses compared to the SCB11 series.
How does the insulation temperature class affect load loss?
Load loss values vary depending on the operating temperature limit of the insulation class used: Class B (100°C), Class F (120°C), and Class H (145°C). Higher insulation classes allow the transformer to run safely at higher thermal limits, altering the load loss parameters accordingly.
Why do dimensions and weights in the tables vary slightly?
Due to continuous technology upgrades, structural optimizations, and potential customization requirements (such as enclosure types or terminal configurations), physical dimensions and overall weights are subject to change. Always verify the manufacturer's outline drawing before finalizing installation spaces.
What connection group label is standard for these transformers?
The standard connection group label for these three-dimensional triangle core transformers is Dyn11, which provides excellent performance in handling unbalanced loads and suppressing third harmonics.