Leave Your Message

China Suppliers Factory: GTXGN-12 AC Metal Solid Insulated Ring Main Unit for Reliable Power Distribution

,

Overview

,

The GTXGN-12 AC Metal Solid Insulated Ring Main Unit is an advanced, fully insulated, and maintenance-free switchgear solution designed for reliable performance in various environments. This product features a completely sealed design, ensuring that all high-voltage live components are protected with top-quality insulating epoxy resin materials. The innovative construction integrates the vacuum arc extinguishing chamber, main conductive circuit, and insulating support into a single compact unit, connected through fully insulated solid busbars. This design guarantees that the switchgear remains unaffected by external environmental factors, enhancing operational reliability and personnel safety.

,

Suitable for a 50Hz, 12 kV power system, the GTXGN-12 is widely adopted in industrial and civilian cable ring networks and distribution terminal projects across China. It is ideally suited for urban residential area distribution, small substations, switching stations, cable branching boxes, and box-type substations. This versatile equipment is also applicable in various settings, including shopping malls, airports, subways, wind power generation sites, hospitals, stadiums, railways, and tunnels.

,

Thanks to its fully insulated, completely sealed, and fully shielded features, this ring main unit excels in harsh conditions such as high altitudes, extreme temperatures, humidity, and severe pollution. As a trusted factory in the industry, we are committed to providing reliable electrical solutions, making us a top choice among suppliers in the market.

,

    Product Categories
    The switches are categorized based on type into Load Switch with Ground Assembly (C Module), Load Switch without Ground Assembly (CB Module), Circuit Breaker with Ground Assembly (V Module), Circuit Breaker without Ground Assembly (VB Module), Circuit Breaker Link Switch (VZ Module), Load Switch + Fuse Composite Apparatus Switch Assembly (F Module), and Isolating Switch Assembly (G Module).
    Model and Definitions
    Model and Definitions
    Application Conditions
    Environmental Temperature: -45℃ to +45℃
    Humidity: Maximum Average Relative Humidity, Daily Average≤95%, Monthly Average≤90%
    Altitude: ≤4000 meters
    Seismic Resistance: 8 degrees
    Level of Protection: Live Parts Sealed IP67, Fuse Tubes IP67, Switch Cabinet Housing IP4X
    Standards for Implementation
    IEC62271-1-2007 "High-Voltage Switchgear and Controlgear - Part 1: General Specifications"
    IEC620071-200-2003 "AC Metal-Enclosed Switchgear and Controlgear for 1-52kV"
    GB3906-2006 "AC Metal-Enclosed Switchgear and Controlgear for 3.6-40.5kV"
    GB/T11022-1999 "Common Technical Conditions for High-Voltage Switchgear and Controlgear Standards"
    GB1984-2003 "High-Voltage AC Circuit Breakers"
    GB1985-2004 "High-Voltage AC Disconnectors and Earthing Switches"
    GB3804-2004 "High-Voltage AC Load Switches for 3.6kV to 40.5kV"
    DL/T404-2007 "AC Metal-Enclosed Switchgear and Controlgear for 3.6kV-40.5kV"
    DIJT5932006 "Common Technical Conditions for High-Voltage Switchgear and Controlgear Standards"
    Q/GDW730-2012 "Technical Conditions for 12kV Solid Insulated Ring Main Units"
    Technical Parameters
    Parameters of Switchgear
    No. Units Parameters
    Nominal Voltage KV 12
    Rated Frequency Hz 50
    Rated Currency A 630 1250
    Nominal Insulation Level Power Frequency Withstand Voltage Break Point KV 48
    Phase-to-Phase KV 42
    Relative KV 42
    Lighting Impulse Withstand Voltage Break Point KV 85
    Phase-to-Phase KV 75
    Relative KV 75
    Rated Short-circuit Breaking Current(1s) KA 25 31.5
    Rated Short-time Withstand Current(4s) KA 25 31.5
    Rated Peak Withstand Current(lp) KA 36 80
    Rated Circuit Making Current(Peak)(1ma) KA 36 80
    Level of Protection for Shell IP4X
    Operation Mode Spring-operated
    Isolation Ground Switch Technical Parameters
    No. Items Units Parameters
    1 Nominal Voltage kV 12
    2 Rated Currency A 630 1250
    3 4S Rated Short-time Withstand Current (Valid Value) kA 25 31.5
    4 Rated Peak Withstand Current (Peak) kA 63 80
    5 1min Power Frequency Withstand Voltage Phase-to-Phase and Ground kV 42
    Isolation Break Point 48
    6 Rated Lighting Impulse Withstand Voltage Phase-to-Phase and Ground kV 75
    Isolation Break Point 85
    7 Main Switch Machinery Service Life Time 3000
    8 Ground Switch Machinery Service Life Time 3000
    Safety and Environmental Protection
    Isolation Knife Visible Break Point
    The cabinet features a prominent visible window for the Isolation Break Point, allowing personnel to observe the three working positions: isolation engaged, isolation disengaged, and grounding engaged. This design facilitates the on-site staff in determining the position of the isolation knife, ensuring a high level of safety.
    Internal Arc Design
    Internal Arc Pressure Valve: When an arc occurs inside the product, the pressure will be released through this valve, directing the arc away into the cable trench to prevent accidental injury to operators.
    Green and Environmentally Friendly
    Designed with environmentally friendly materials, this product does not use SF6 gas as an arc extinguishing medium or insulation, thus avoiding environmental pollution. The one-time circuit design minimizes contact points, ensuring low energy consumption during operation.
    External Dimensions
    External Dimensions
    Model Width (mm) Depth(mm) Height(mm)
    Load Switch PT Cabinet (CPT) 500 950 1650
    Circuit Breaker Cabinet (VB) 400 950 1650
    Circuit Breaker Cabinet(V) 400 950 1650
    Circuit Breaker Bus Coupling Cabinet (VZ) 400 950 1650
    Busbar Lifting Cabinet(G) 400 950 1650
    Load Switch Fuse Combination Cabinet (F) 500 950 1650
    Frequently Asked Questions (FAQ)
    Q1: What types of modules are available in these product categories?
    A: The switches are categorized into Load Switch with Ground Assembly (C Module), Load Switch without Ground Assembly (CB Module), Circuit Breaker with Ground Assembly (V Module), Circuit Breaker without Ground Assembly (VB Module), Circuit Breaker Link Switch (VZ Module), Load Switch + Fuse Composite Apparatus Switch Assembly (F Module), and Isolating Switch Assembly (G Module).
    Q2: What environmental conditions are required for operating this switchgear?
    A: The equipment is designed to operate in temperatures ranging from -45℃ to +45℃, with a maximum daily average relative humidity of ≤95% (monthly average ≤90%), at altitudes up to 4000 meters, and with seismic resistance up to 8 degrees.
    Q3: What are the protection levels for the switch cabinet and live parts?
    A: The live parts and fuse tubes are sealed to IP67 standards, while the switch cabinet housing has a protection level of IP4X.
    Q4: Does this product use SF6 gas for insulation?
    A: No, this product is designed with green, environmentally friendly materials and does not use SF6 gas as an arc extinguishing medium or insulation, thereby avoiding environmental pollution.
    Q5: How does the internal arc design protect operators?
    A: It features an Internal Arc Pressure Valve. If an arc occurs internally, the pressure is released through this valve and directed away into the cable trench, preventing accidental injury to operators on site.
    Q6: What are the standard dimensions for the Circuit Breaker Cabinet (VB)?
    A: The Circuit Breaker Cabinet (VB) has a width of 400 mm, a depth of 950 mm, and a height of 1650 mm.

    Leave Your Message

    AI Helps Write