China Suppliers Factory for HXGN17-12 Box-Type Fixed AC Metal-Enclosed Ring Network Switchgear 12kV
Standards
Model and Definitions
Conditions of Use
Major Technical Specifications
| No. | Items | Units | FN12-12 | FZN25-12 | |
| 1 | Nominal Voltage | kV | 12 | ||
| 2 | 1min Power Frequency Withstand Voltage | kV | Ground and phase-to-phase 42; Isolation Break Point 48 | ||
| 3 | Lightning Impulse Voltage (Peak) | Ground and phase-to-phase 75; Isolation Break Point 85 | |||
| 4 | Rated Frequency | Hz | 50 | ||
| 5 | Load Switch | Rated Current | A | 630 | |
| 6 | Rated Current Switching Life | Time | Not less than 100 | ||
| 7 | Breaking Capacity of No-load Transformer | kVA | 1250 | ||
| 8 | Rated Thermal Stability Current | kA/s | 20/4; Ground switch 20/2 | ||
| 9 | Rated Dynamic Stability Current (Peak) | kA | 50 | ||
| 10 | Rated Circuit Making Current (Peak) | 50 | |||
| 11 | Fuse Rated Current | A | 125 | ||
| 12 | Composite Apparatus | Rated Transfer Current | A | 870 | |
| 13 | Rated Short-circuit Breaking Current | kA | 20 | ||
| 14 | Compatible Fuse Model | S □ LAJ-12 | |||
| 15 | Machinery Service Life | Times | 2000 | 10000 | |
| 16 | Auxiliary Circuit 1min Power Frequency Withstand Voltage | kV | 2 | ||
| 17 | Electric Operating Mechanism Working Voltage | V | AC/DC 220; 110 | ||
| 18 | Level of Protection | IP2X | |||
Structural Features
External Dimensions
Ordering Notes
◆ When placing an order, the following technical information must be provided:
Frequently Asked Questions (FAQ)
It conforms to GB 3906-2006, IEC 60298-1990, and GB/T 11022-2011 standards for high-voltage and metal-enclosed switchgear and controlgear.
The ambient temperature range is -25℃ to +40℃, with an altitude not exceeding 1000m and relative humidity under 95% (daily average). It must be operated in areas free from fire, explosive risks, corrosive/flammable gases, and severe vibrations.
It can accommodate FN12-12 pneumatic load switches/composite apparatus or FZN25-12 vacuum load switches/composite apparatus.
The machinery service life is 2,000 operations for the FN12-12 model and up to 10,000 operations for the FZN25-12 model.
It integrates a complete "five prevention" mechanical interlock preventing incorrect operations between the load switch, grounding switch, and front door, along with electromagnetic locking for cable entry power safety.
You should provide the main wiring scheme number, single-line diagrams, voltage/current ratings, switch cabinet layout, component models/quantities, and any specific environmental condition requirements.