Overview

The HXGN17-12 Box-Type Fixed AC Metal-Enclosed Ring Network Switchgear, often known as a ring network cabinet, is designed to operate efficiently at a nominal voltage of 12kV and a frequency of 50Hz. This advanced high-voltage switchgear is ideal for three-phase AC ring networks, terminal distribution networks, and industrial power supply systems. It is crucial for the reception, distribution, and protection of electrical energy, as well as being suitable for installation in box-type substations.
Manufactured by leading China suppliers, this equipment adheres to GB3906 standards for 3.6~40.5 kV AC metal-enclosed switchgear and control equipment while also complying with international IEC298 standards. It boasts a five-proof interlocking function that significantly enhances operational safety and reliability. As a trusted factory in the industry, we provide top-quality products to meet your electrical needs.

    Standards

    ◇
    GB 3906-2006 "AC Metal-Enclosed Switchgear and Controlgear for Rated Voltages from 3.6 kV to 40.5 kV"
    ◇
    IEC 60298-1990 "Metal-Enclosed Switchgear and Controlgear for Rated Voltages Above 1 kV and Up to 52 kV"
    ◇
    GB/T 11022-2011 "Common Technical Requirements for High-Voltage Switchgear and Controlgear Standards"

    Model and Definitions

    product-description1

    Conditions of Use

    ◇
    Ambient Temperature: Upper limit +40℃, Lower limit -25℃;
    ◇
    Altitude: Not exceeding 1000m;
    ◇
    Relative Humidity: Daily average not exceeding 95%, Monthly average not exceeding 90%;
    ◇
    Locations free from fire, explosion hazards, and severe vibrations;
    ◇
    Surrounding air must not contain corrosive or flammable gases, water vapor, or conductive dust, avoiding significant contamination.

    Major Technical Specifications

    No. Items Units FN12-12 FZN25-12
    1 Nominal Voltage kV 12
    2 1min Power Frequency Withstand Voltage kV Ground and phase-to-phase 42; Isolation Break Point 48
    3 Lightning Impulse Voltage (Peak) Ground and phase-to-phase 75; Isolation Break Point 85
    4 Rated Frequency Hz 50
    5 Load Switch Rated Current A 630
    6 Rated Current Switching Life Time Not less than 100
    7 Breaking Capacity of No-load Transformer kVA 1250
    8 Rated Thermal Stability Current kA/s 20/4; Ground switch 20/2
    9 Rated Dynamic Stability Current (Peak) kA 50
    10 Rated Circuit Making Current (Peak) 50
    11 Fuse Rated Current A 125
    12 Composite Apparatus Rated Transfer Current A 870
    13 Rated Short-circuit Breaking Current kA 20
    14 Compatible Fuse Model S □ LAJ-12
    15 Machinery Service Life Times 2000 10000
    16 Auxiliary Circuit 1min Power Frequency Withstand Voltage kV 2
    17 Electric Operating Mechanism Working Voltage V AC/DC 220; 110
    18 Level of Protection IP2X

    Structural Features

    ◇
    The fully assembled structure is lightweight and aesthetically pleasing, allowing for arbitrary combinations and installations, facilitating infinite expansion.
    ◇
    It can be equipped with the FN12-12 type pneumatic Load Switch, Composite Apparatus, or the FZN25-12 type vacuum Load Switch, Composite Apparatus. It is compact, maintenance-free, features a three-phase linkage structure, and has a distinct Isolation Break Point.
    ◇
    The installation method for the Load Switch and Composite Apparatus is flexible, allowing for left-side, right-side, upright, and inverted installations (FZN25 cannot be inverted).
    ◇
    It supports both manual and electric operation and can have remote control capabilities.
    ◇
    Equipped with a complete and reliable mechanical linkage and interlocking device, it fully meets the "five prevention" functions. When the Load Switch is closed, the grounding switch cannot close, and the front door cannot be opened; when the Load Switch is opened, the grounding switch can close, and the front door can be opened when the grounding switch is closed; when the grounding switch is closed, the Load Switch cannot close, but the front door can be opened; when the grounding switch is opened, the Load Switch can open and close, and the front door cannot be opened; when the cable enters from below, if there is power at the entry, regardless of whether the Load Switch is in the closed or open position, the electromagnetic lock controls the front door, preventing it from being opened (except for emergency unlocking with a special key).
    ◇
    The Load Switch uses interlocking protective insulated valves or transparent insulated covers to shield live contacts, ensuring personal safety.
    ◇
    It employs front operation and maintenance, reliably wall-mounted.
    ◇
    The front door is equipped with a viewing window to clearly observe the working conditions of the components inside the cabinet.

    External Dimensions

    product-description2

    Ordering Notes

    ◆ When placing an order, the following technical information must be provided:

    ◇
    Main wiring scheme number, purpose, and single-line system diagram, Nominal Voltage, Rated Current, Rated Short-circuit Breaking Current / layout of the distribution room and arrangement configuration diagram of the switch cabinet, etc.;
    ◇
    Requirements for the control, measurement, and protection functions of the switch cabinet, as well as the requirements and schematic diagrams for other locking and automatic devices;
    ◇
    Model, specifications, and quantity of the main electrical components in the switch cabinet;
    ◇
    If the switch cabinet is used in special environmental conditions, this should be detailed during the order placement.

    Frequently Asked Questions (FAQ)

    Q1 What standards does this switchgear conform to?

    It conforms to GB 3906-2006, IEC 60298-1990, and GB/T 11022-2011 standards for high-voltage and metal-enclosed switchgear and controlgear.

    Q2 What are the operational temperature and environmental limits?

    The ambient temperature range is -25℃ to +40℃, with an altitude not exceeding 1000m and relative humidity under 95% (daily average). It must be operated in areas free from fire, explosive risks, corrosive/flammable gases, and severe vibrations.

    Q3 What types of load switches can be installed?

    It can accommodate FN12-12 pneumatic load switches/composite apparatus or FZN25-12 vacuum load switches/composite apparatus.

    Q4 What is the mechanical service life difference between FN12-12 and FZN25-12?

    The machinery service life is 2,000 operations for the FN12-12 model and up to 10,000 operations for the FZN25-12 model.

    Q5 How does the mechanical interlock ensure operational safety?

    It integrates a complete "five prevention" mechanical interlock preventing incorrect operations between the load switch, grounding switch, and front door, along with electromagnetic locking for cable entry power safety.

    Q6 What critical details are needed when placing an order?

    You should provide the main wiring scheme number, single-line diagrams, voltage/current ratings, switch cabinet layout, component models/quantities, and any specific environmental condition requirements.