0102030405
China SRM6-12 Fully Insulated Gas-Insulated Ring Main Unit - Reliable Suppliers & Factory for 10kV/6kV Systems
Model and Definitions
For example:
◇ SRM6-12-C/630DL indicates a load switch cabinet with a nominal voltage of 12kV, rated current of 630A, right-side expansion, and left-side cable entry and exit method.
◇ SRM6-12-CF/6301R signifies a combination unit formed by a load switch cabinet and a fuse combination cabinet. It has a bus voltage of 12kV and a bus current of 630A, with left-side expansion and right-side cable entry and exit method.
Performance Indexes
| Unit Code | Definition | Unit Code | Definition | ||
| C | Standard Single Set Load Switch Unit | - | Busbar Top Insulator | ||
| F | Load Switch-Fuse Composite Apparatus Unit | SL | Bus Coupler Unit | ||
| V | Circuit Breaker Unit | M | Measurement Unit | ||
| D | Cable Entry Unit (Without Switch) | PT | PT UNIT | ||
| + | Busbar Side lnsulator | 1K2(4) | Load Switch Unit with Double Insulator | ||
Technical Specifications
| Model | C Module | F Module | V Module | CB Module | ||
| Compound Switch | Composite Apparatus | Vacuum Switch | Isolation/ Earthing Switch | Vacuum Breaker | Isolation/ Earthing Switch | |
| Nominal Voltage (KV) | 12 | 12 | 12 | 12 | 12 | 12 |
| Rated Frequency (Hz) | 50 | 50 | 50 | 50 | 50 | 50 |
| Power Frequency Withstand Voltage (Interphase/Terminal) (KV) | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 |
| Lighting lmpulse Withstand Voltage (kV) | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
| Rated Currency (A) | 630 | Note ¹ | 630 | 1250/630 | ||
| Rated Closed Loop Breaking Current (A) | 630 | |||||
| Rated Cable Charge Breaking Current (A) | 135/135 | |||||
| Rated Circuit Making Current (Peak) (A) | 50 | 80 | ||||
| Rated Peak Withstand Current (kA) | 50 | |||||
| Rated Short-time Withstand Current (:A/3s) | 20 | |||||
| Rated Short-circuit Breaking Current (kA) | 31.5 | 20 | 25 | |||
| Rated Transfer Current (A) | 1750 | |||||
| Maximum Current for Compatible Fuses (A) | 125 | |||||
| Loop Resistance (Ω) | ≤ 300 | ≤ 600 | ||||
| Machinery Service Life (Times) | 5000 | 3000 | 5000 | 2000 | 5000 | 5000 |
Note: 1) It depends on the current rating of the fuse.
SRM 6 - 1 2 Gas-Insulated Switchgear Structure and Dimensions
Frequently Asked Questions (FAQ)
Q
What does the model name "SRM6-12-C/630DL" represent?
It represents a load switch cabinet featuring a nominal voltage of 12kV, a rated current of 630A, designed with right-side expansion capability, and employing a left-side cable entry and exit configuration.
Q
What do the unit codes "C", "F", and "V" stand for in the performance indexes?
In the performance index, "C" stands for the Standard Single Set Load Switch Unit, "F" represents the Load Switch-Fuse Composite Apparatus Unit, and "V" represents the Circuit Breaker Unit.
Q
What is the nominal voltage and rated frequency for the SRM6-12 modules?
All modules (including C, F, V, and CB modules) have a nominal voltage rating of 12 kV and operate at a rated frequency of 50 Hz.
Q
What is the rated current for the F Module (Composite Apparatus)?
The rated current for the F Module is not fixed; it directly depends on the specific current rating of the compatible fuse used.
Q
What is the mechanical service life of the C Module compared to the F Module?
The C Module (Compound Switch) has a mechanical service life of 5000 operations, whereas the F Module (Composite Apparatus) has a mechanical service life of 3000 operations.