0102030405
China SRM6-12 Fully Insulated Gas-Insulated Ring Main Unit - Reliable Supplier & Factory for 10kV/6kV Systems
Model and Definitions
For example:
SRM6-12-C/630DL indicates a load switch cabinet with a nominal voltage of 12kV, rated current of 630A, right-side expansion, and left-side cable entry and exit method.
SRM6-12-CF/6301R signifies a combination unit formed by a load switch cabinet and a fuse combination cabinet. It has a bus voltage of 12kV and a bus current of 630A, with left-side expansion and right-side cable entry and exit method.
Performance Indexes
| Unit Code | Definition | Unit Code | Definition | ||
| C | Standard Single Set Load Switch Unit | - | Busbar Top Insulator | ||
| F | Load Switch-Fuse Composite Apparatus Unit | SL | Bus Coupler Unit | ||
| V | Circuit Breaker Unit | M | Measurement Unit | ||
| D | Cable Entry Unit (Without Switch) | PT | PT UNIT | ||
| + | Busbar Side lnsulator | 1K2(4) | Load Switch Unit with Double Insulator | ||
Technical Specifications
| Model | C Module | F Module | V Module | CB Module | ||
| Compound Switch | Composite Apparatus | Vacuum Switch | Isolation/ Earthing Switch | Vacuum Breaker | Isolation/ Earthing Switch | |
| Nominal Voltage (KV) | 12 | 12 | 12 | 12 | 12 | 12 |
| Rated Frequency (Hz) | 50 | 50 | 50 | 50 | 50 | 50 |
| Power Frequency Withstand Voltage (Interphase/Terminal) (KV) | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 |
| Lighting lmpulse Withstand Voltage (kV) | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
| Rated Currency (A) | 630 | Note ¹ | 630 | 1250/630 | ||
| Rated Closed Loop Breaking Current (A) | 630 | |||||
| Rated Cable Charge Breaking Current (A) | 135/135 | |||||
| Rated Circuit Making Current (Peak) (A) | 50 | 80 | ||||
| Rated Peak Withstand Current (kA) | 50 | |||||
| Rated Short-time Withstand Current (kA/3s) | 20 | |||||
| Rated Short-circuit Breaking Current (kA) | 31.5 | 20 | 25 | |||
| Rated Transfer Current (A) | 1750 | |||||
| Maximum Current for Compatible Fuses (A) | 125 | |||||
| Loop Resistance (μΩ) | ≤ 300 | ≤ 600 | ||||
| Machinery Service Life (Times) | 5000 | 3000 | 5000 | 2000 | 5000 | 5000 |
Note: 1) It depends on the current rating of the fuse.
SRM 6 - 1 2 Gas-Insulated Switchgear Structure and Dimensions
Frequently Asked Questions (FAQ)
What does the model name SRM6-12-C/630DL stand for?
It indicates a load switch cabinet with a nominal voltage of 12kV, a rated current of 630A, designed with right-side expansion, and featuring a left-side cable entry and exit configuration.
What are the different module codes in the SRM6-12 performance index?
The main module codes include C (Standard Single Set Load Switch Unit), F (Load Switch-Fuse Composite Apparatus Unit), V (Circuit Breaker Unit), and D (Cable Entry Unit without Switch).
What is the nominal voltage and frequency of the SRM6-12 switchgear?
The SRM6-12 Gas-Insulated Switchgear operates at a nominal voltage of 12 kV and a rated frequency of 50 Hz.
What is the mechanical service life of the C Module and V Module?
The Compound Switch in the C Module and the Vacuum Switch in the V Module both have a machinery service life of 5000 operations. The isolation/earthing switch within the V Module has a service life of 2000 operations.
How is the rated current for the F Module (Composite Apparatus) determined?
The rated current for the F Module (Load Switch-Fuse Composite Apparatus Unit) depends directly on the current rating of the compatible fuse installed.