China KYN61-40.5(Z) Armored Removable AC Metal-Enclosed Switchgear - Reliable Suppliers & Factory Solutions

,

Overview

,

The KYN61-40.5 armored removable AC metal-enclosed switchgear, also known as the switch cabinet, is a state-of-the-art three-phase AC distribution device designed for indoor applications with a frequency of 50Hz and a nominal voltage of 40.5kV. Manufactured in China, this switch cabinet is widely used in power plants, substations, and industrial enterprises for the efficient reception and distribution of electrical energy. It offers essential functions such as control, protection, and monitoring of electrical circuits, making it ideal for locations that require frequent operations. As a leading product from trusted suppliers and factories, this switch cabinet complies with key industry standards, including GB3906-2006, GB/T11022-1999, and DL/T 404-2007, ensuring reliability and performance.

,

    Main Features

    • The cabinet structure adopts an assembled design, with the circuit breaker featuring a handcart ground structure;
    • Equipped with a newtype of composite insulated vacuum circuit breaker, characterized by good interchangeability and easy replacement;
    • The handcart frame is equipped with a screw nut propulsion mechanism, allowing for easy movement of the handcart and preventing damage from accidental operation;
    • All operations can be performed with the cabinet door closed;
    • Interlocking between the main switch, handcart, and switch cabinet door adopts a mandatory mechanical interlocking method, satisfying the "five prevention" functions;
    • The cable chamber has ample space, allowing for multiple cable connections;
    • A rapid grounding switch is provided for grounding and closing short-circuit loops;
    • The shell has a Level of Protection IP3X, while the handcart chamber door opened state has a Level of Protection IP2X;
    • The product complies with GB3906-2006, DL/T404-2007, and refers to the international standard IEC298.

    Use Environment Conditions

    • Ambient temperature: Upper limit +40℃, with the average value measured over 24 hours not exceeding 35℃; lower limit -10℃;
    • Altitude: Altitude not exceeding 1000m;
    • Relative Humidity: Daily average not exceeding 95%, monthly average not exceeding 90%;
    • Earthquake intensity: Not exceeding 8 degrees;
    • Water vapor pressure: Daily average not exceeding 2.2kPa, monthly average not exceeding 1.8kPa;
    • Surrounding environment: Locations free from fire, explosion hazards, severe pollution, chemical corrosion, and intense vibrations.

    Technical Parameters

    Items Units Value
    Rated Operating Voltage Opening Solenoid V DC220/110 AC220/110
    Closing Coil
    Rated Operating Current Opening Solenoid A 0.96(220V)1.05(110V)
    Closing Coil
    Energy Storage Motor Power W 230
    Nominal Voltage of Stored Energy Electric Machinery V DC220/110 AC220/110
    Stored Energy Time S ≤12

    Technical Parameters

    Technical Parameters of Vacuum Switch Cabinet
    No. Items Units Value
    1 Nominal Voltage KV 40.5
    2 Rated Currency A 1250 1600 2000
    3 Rated Frequency Hz 50
    4 Rated Short-time Withstand Current KA 20 25 31.5
    5 Rated Peak Withstand Current KA 50 63 80
    6 Rated Power Frequency Withstand Voltage KV 95/1min
    7 Rated Lighting Impulse Withstand Voltage KV 185
    8 Rated Short-circuit Period S 4
    9 Level of Protection IP3X
    Main Technical Parameters of Vacuum Short-circuit
    No. Items Units Value
    1 Nominal Voltage KV 40.5
    2 Rated Frequency Hz 50
    3 Rated Power Frequency Withstand Voltage KV 95/1min
    4 Rated Lighting Impulse Withstand Voltage KV 185
    5 Rated Currency A 1250 1600 2000
    6 Rated Short-time Withstand Current KA 20 25 31.5
    7 Rated Short-circuit Breaking Current KA 20 25 31.5
    8 Rated Peak Withstand Current KA 50 63 80
    9 Rated Short-circuit Period ms 4
    10 Opening Time ms 30≤t≤ 60
    11 ClosingTime ms 50 <t≤ 100
    12 Rated Short-circuit Breaking Current Times Time 20
    13 Machinery Service Life Time 10000
    product-description1

    Switch Cabinet Dimensions

    product-description2

    Installation of Switch Cabinet

    • Height of the electrical room: ≥4500mm;
    • Distance from the back of the cabinet to the wall: ≥1500mm;
    • Flatness of the foundation structure: ≤1mm/ m²;
    • The embedded channel steel of the foundation should not exceed 3mm above the ground;
    • Can be fixed to the foundation using bolts or welding methods;
    • The weight of the switch cabinet is approximately 1800kg;
    • Width of the switch cabinet operational corridor (single row): ≥3000mm, double row (facing each other) :≥4000mm.

    Ordering Instructions

    WHEN PLACING AN ORDER, PLEASE SPECIFY:
    • Main circuit scheme number, purpose, single-line system diagram, layout diagram, and floor plan of the distribution room;
    • Auxiliary circuit wiring schematic and terminal arrangement diagram;
    • Model, specifications, and quantity of electrical components within the switchgear;
    • Requirements for control, measurement, and protection functions of the switchgear, as well as any other interlocking and automatic device requirements;
    • If busbar connections are needed between switchgear or incoming cabinets, please provide specific data such as the rated current capacity of the busbar, span of the busbar, and height above ground;
    • If accessories or spare parts are required, please specify the types and quantities;
    • If the switchgear is to be used in special environmental conditions, please detail these conditions when placing the order.

    Frequently Asked Questions

    What are the main design features of this switch cabinet?
    The cabinet features an assembled design with a handcart ground structure circuit breaker. It is equipped with a new type of composite insulated vacuum circuit breaker for easy replacement and incorporates a mandatory mechanical interlocking method to ensure the "five prevention" safety functions.
    What are the standard ambient temperature limits for installation?
    The standard operating ambient temperature is from a lower limit of -10℃ to an upper limit of +40℃, with the average temperature measured over 24 hours not exceeding 35℃.
    What is the level of protection (IP rating) for this switch cabinet?
    The outer shell has a Level of Protection of IP3X. When the handcart chamber door is opened, the internal level of protection is IP2X.
    What are the dimensions and space requirements for the electrical installation room?
    The electrical room requires a minimum height of ≥4500mm. The distance from the back of the cabinet to the wall must be ≥1500mm. The operational corridor width must be ≥3000mm for a single row and ≥4000mm for a double row facing each other.
    What information should be provided when placing an order?
    When ordering, you should specify the main circuit scheme, single-line system diagram, distribution room layout, auxiliary circuit schematics, components specifications, control/protection requirements, and any special environmental conditions if applicable.