Leave Your Message

China KYN61-40.5 Armored Removable AC Metal-Enclosed Switchgear - Reliable Suppliers and Factory Solutions

,

Product Overview

,

The KYN61-40.5 armored removable AC metal-enclosed switchgear, commonly referred to as a switch cabinet, is an advanced three-phase AC distribution device designed for indoor applications with a frequency of 50Hz and a nominal voltage of 40.5kV. Manufactured in China, this switch cabinet is ideal for power plants, substations, and industrial facilities, providing reliable reception and distribution of electrical energy.

,

This state-of-the-art switch cabinet excels in functions such as circuit control, protection, and monitoring, making it particularly suitable for environments that demand frequent operation. Adhering to industry standards including GB3906-2006, GB/T11022-1999, and DL/T 404-2007, the KYN61-40.5 is a top choice among suppliers and factory operators looking for efficiency and durability in electrical distribution. Experience superior performance and reliability with this essential component of your electrical system.

,

    Main Features

    • The cabinet structure adopts an assembled design, with the circuit breaker featuring a handcart ground structure;
    • Equipped with a newtype of composite insulated vacuum circuit breaker, characterized by good interchangeability and easy replacement;
    • The handcart frame is equipped with a screw nut propulsion mechanism, allowing for easy movement of the handcart and preventing damage from accidental operation;
    • All operations can be performed with the cabinet door closed;
    • Interlocking between the main switch, handcart, and switch cabinet door adopts a mandatory mechanical interlocking method, satisfying the "five prevention" functions;
    • The cable chamber has ample space, allowing for multiple cable connections;
    • A rapid grounding switch is provided for grounding and closing short-circuit loops;
    • The shell has a Level of Protection IP3X, while the handcart chamber door opened state has a Level of Protection IP2X;
    • The product complies with GB3906-2006, DL/T404-2007, and refers to the international standard IEC298.

    Use Environment Conditions

    • Ambient temperature: Upper limit +40℃, with the average value measured over 24 hours not exceeding 35℃; lower limit -10℃;
    • Altitude: Altitude not exceeding 1000m;
    • Relative Humidity: Daily average not exceeding 95%, monthly average not exceeding 90%;
    • Earthquake intensity: Not exceeding 8 degrees;
    • Water vapor pressure: Daily average not exceeding 2.2kPa, monthly average not exceeding 1.8kPa;
    • Surrounding environment: Locations free from fire, explosion hazards, severe pollution, chemical corrosion, and intense vibrations.

    Technical Parameters

    Items Units Value
    Rated Operating Voltage Opening Solenoid V DC220/110 AC220/110
    Closing Coil
    Rated Operating Current Opening Solenoid A 0.96(220V) 1.05(110V)
    Closing Coil
    Energy Storage Motor Power W 230
    Nominal Voltage of Stored Energy Electric Machinery V DC220/110 AC220/110
    Stored Energy Time S ≤12

    Technical Parameters Details

    Technical Parameters of Vacuum Switch Cabinet
    No. Items Units Value
    1 Nominal Voltage KV 40.5
    2 Rated Currency A 1250 1600 2000
    3 Rated Frequency Hz 50
    4 Rated Short-time Withstand Current KA 20 25 31.5
    5 Rated Peak Withstand Current KA 50 63 80
    6 Rated Power Frequency Withstand Voltage KV 95/1min
    7 Rated Lighting Impulse Withstand Voltage KV 185
    8 Rated Short-circuit Period S 4
    9 Level of Protection IP3X
    Main Technical Parameters of Vacuum Short-circuit
    No. Items Units Value
    1 Nominal Voltage KV 40.5
    2 Rated Frequency Hz 50
    3 Rated Power Frequency Withstand Voltage KV 95/1min
    4 Rated Lighting Impulse Withstand Voltage KV 185
    5 Rated Currency A 1250 1600 2000
    6 Rated Short-time Withstand Current KA 20 25 31.5
    7 Rated Short-circuit Breaking Current KA 20 25 31.5
    8 Rated Peak Withstand Current KA 50 63 80
    9 Rated Short-circuit Period ms 4
    10 Opening Time ms 30 ≤ t ≤ 60
    11 Closing Time ms 50 < t ≤ 100
    12 Rated Short-circuit Breaking Current Times Time 20
    13 Machinery Service Life Time 10000
    product-description1

    Switch Cabinet Dimensions

    product-description2

    Installation of Switch Cabinet

    • Height of the electrical room: ≥4500mm;
    • Distance from the back of the cabinet to the wall: ≥1500mm;
    • Flatness of the foundation structure: ≤1mm/ m²;
    • The embedded channel steel of the foundation should not exceed 3mm above the ground;
    • Can be fixed to the foundation using bolts or welding methods;
    • The weight of the switch cabinet is approximately 1800kg;
    • Width of the switch cabinet operational corridor (single row): ≥3000mm, double row (facing each other): ≥4000mm.

    Ordering Instructions

    WHEN PLACING AN ORDER, PLEASE SPECIFY:
    • Main circuit scheme number, purpose, single-line system diagram, layout diagram, and floor plan of the distribution room;
    • Auxiliary circuit wiring schematic and terminal arrangement diagram;
    • Model, specifications, and quantity of electrical components within the switchgear;
    • Requirements for control, measurement, and protection functions of the switchgear, as well as any other interlocking and automatic device requirements;
    • If busbar connections are needed between switchgear or incoming cabinets, please provide specific data such as the rated current capacity of the busbar, span of the busbar, and height above ground;
    • If accessories or spare parts are required, please specify the types and quantities;
    • If the switchgear is to be used in special environmental conditions, please detail these conditions when placing the order.

    Frequently Asked Questions

    Q1: What standards do these switch cabinets comply with?
    Our products fully comply with GB3906-2006 and DL/T404-2007 standards, and refer directly to the international standard IEC298 to ensure reliable safety and performance.
    Q2: What are the protection ratings for the switch cabinet shell and handcart chamber?
    The external shell of the switch cabinet features an IP3X protection rating. When the handcart chamber door is opened, the protection level is rated at IP2X.
    Q3: What is the recommended height and space layout for installation?
    The installation room requires a height of ≥4500mm, with the back of the cabinet placed ≥1500mm from the wall. The operational corridor width must be ≥3000mm for a single row and ≥4000mm for double-row facing configurations.
    Q4: What are the ambient temperature limits for normal operation?
    The switchgear is designed for environments with an upper ambient temperature limit of +40℃ (with a 24-hour average not exceeding 35℃) and a lower limit of -10℃.
    Q5: How is accidental operation prevented in this switch cabinet?
    It utilizes a mandatory mechanical interlocking method between the main switch, handcart, and switch cabinet door to fulfill the standard "five prevention" safety functions. Additionally, all operations can be safely performed with the cabinet door closed.

    Leave Your Message