Overview

,

The HXGN17-12 Box-Type Fixed AC Metal-Enclosed Ring Network Switchgear, commonly known as a ring network cabinet, is a reliable solution with a nominal voltage of 12kV and a rated frequency of 50Hz. Designed specifically for three-phase AC ring networks, terminal distribution networks, and industrial power supply systems, this high-voltage equipment is essential for efficient electrical energy reception and distribution while providing critical protection. It is also suitable for installation in box-type substations.
Manufactured in China, this equipment adheres to GB3906 standards for 3.6~40.5 kV AC metal-enclosed switchgear and control equipment, fulfilling international standards IEC29Additionally, it incorporates a five-proof interlocking function, enhancing operational safety and reliability. As a leading supplier in the industry, our factory ensures that the HXGN17-12 meets the highest quality standards for optimal performance in demanding environments.

,

    Standards

    GB 3906-2006 "AC Metal-Enclosed Switchgear and Controlgear for Rated Voltages from 3.6 kV to 40.5 kV"
    IEC 60298-1990 "Metal-Enclosed Switchgear and Controlgear for Rated Voltages Above 1 kV and Up to 52 kV"
    GB/T 11022-2011 "Common Technical Requirements for High-Voltage Switchgear and Controlgear Standards"

    Model and Definitions

    Model and Definitions of Switchgear

    Conditions of Use

    Ambient Temperature: Upper limit +40℃, Lower limit -25℃;
    Altitude: Not exceeding 1000m;
    Relative Humidity: Daily average not exceeding 95%, Monthly average not exceeding 90%;
    Locations free from fire, explosion hazards, and severe vibrations;
    Surrounding air must not contain corrosive or flammable gases, water vapor, or conductive dust, avoiding significant contamination.

    Major Technical Specifications

    No. Items Units FN12-12 FZN25-12
    1 Nominal Voltage kV 12
    2 1min Power Frequency Withstand Voltage kV Ground and phase-to-phase 42; Isolation Break Point 48
    3 Lightning Impulse Voltage (Peak) Ground and phase-to-phase 75; Isolation Break Point 85
    4 Rated Frequency Hz 50
    5 Load Switch Rated Currency A 630
    6 Rated Current Switching Life Time Not less than 100
    7 Breaking Capacity of No-load Transformer kVA 1250
    8 Rated Thermal Stability Current kA/S 20/4; Ground switch 20/2
    9 Rated Dynamic Stability Current (Peak) kA 50
    10 Rated Circuit Making Current (Peak) 50
    11 Fuse Rated Currency A 125
    12 Composite Apparatus Rated Transfer Current A 870
    13 Rated Short-circuit Breaking Current kA 20
    14 Compatible Fuse Model S □ LAJ-12
    15 Machinery Service Life Time 2000 10000
    16 Auxiliary Circuit 1min Power Frequency Withstand Voltage kV 2
    17 Electric Operating Mechanism Working Voltage V AC/DC 220; 110
    18 Level of Protection IP2X

    Structural Features

    The fully assembled structure is lightweight and aesthetically pleasing, allowing for arbitrary combinations and installations, facilitating infinite expansion.
    It can be equipped with the FN12-12 type pneumatic Load Switch, Composite Apparatus, or the FZN25-12 type vacuum Load Switch, Composite Apparatus. It is compact, maintenance-free, features a three-phase linkage structure, and has a distinct Isolation Break Point.
    The installation method for the Load Switch and Composite Apparatus is flexible, allowing for left-side, right-side, upright, and inverted installations (FZN25 cannot be inverted).
    It supports both manual and electric operation and can have remote control capabilities.
    Equipped with a complete and reliable mechanical linkage and interlocking device, it fully meets the "five prevention" functions. When the Load Switch is closed, the grounding switch cannot close, and the front door cannot be opened; when the Load Switch is opened, the grounding switch can close, and the front door can be opened when the grounding switch is closed; when the grounding switch is closed, the Load Switch cannot close, but the front door can be opened; when the grounding switch is opened, the Load Switch can open and close, and the front door cannot be opened; when the cable enters from below, if there is power at the entry, regardless of whether the Load Switch is in the closed or open position, the electromagnetic lock controls the front door, preventing it from being opened (except for emergency unlocking with a special key).
    The Load Switch uses interlocking protective insulated valves or transparent insulated covers to shield live contacts, ensuring personal safety.
    It employs front operation and maintenance, reliably wall-mounted.
    The front door is equipped with a viewing window to clearly observe the working conditions of the components inside the cabinet.

    External Dimensions

    External Dimensions Diagram

    Ordering Notes

    ◆ When placing an order, the following technical information must be provided:
    Main wiring scheme number, purpose, and single-line system diagram, Nominal Voltage, Rated Current, Rated Short-circuit Breaking Current / layout of the distribution room and arrangement configuration diagram of the switch cabinet, etc.;
    Requirements for the control, measurement, and protection functions of the switch cabinet, as well as the requirements and schematic diagrams for other locking and automatic devices;
    Model, specifications, and quantity of the main electrical components in the switch cabinet;
    If the switch cabinet is used in special environmental conditions, this should be detailed during the order placement.

    Frequently Asked Questions (FAQ)

    What are the main standards complied with by these switchgears?
    The switchgears comply with GB 3906-2006 (for rated voltages 3.6 kV to 40.5 kV), IEC 60298-1990 (for rated voltages above 1 kV up to 52 kV), and GB/T 11022-2011 (common technical requirements for high-voltage switchgear).
    What environmental conditions are required for the installation of this equipment?
    The equipment should be operated in ambient temperatures between -25℃ and +40℃, at altitudes not exceeding 1000m, and with daily relative humidity below 95% (monthly average below 90%). The installation site must be free from fire, explosion hazards, severe vibrations, and corrosive or flammable gases.
    What type of load switches can be fitted in these cabinets?
    They can be configured with the FN12-12 type pneumatic Load Switch / Composite Apparatus, or the FZN25-12 type vacuum Load Switch / Composite Apparatus. Both feature a three-phase linkage structure and a clear Isolation Break Point.
    How does the interlocking safety mechanism protect operators?
    It features a reliable mechanical linkage and interlocking device meeting "five prevention" criteria. For instance, the grounding switch cannot close if the Load Switch is closed, and the front door remains locked via an electromagnetic lock if the incoming cable is energized, preventing accidental contact.
    What is the mechanical service life of the FN12-12 and FZN25-12 switches?
    The FN12-12 switch has a mechanical service life of 2,000 operations, whereas the FZN25-12 switch has a mechanical service life of 10,000 operations.
    What information is needed to place an order?
    You must provide the main wiring scheme number, single-line system diagram, nominal voltage, rated current, rated short-circuit breaking current, layout of the distribution room, control requirements, and details of any special environmental conditions.

    Leave Your Message