Overview

,

The HXGN15-12 box-type fixed metal-enclosed ring network switchgear, commonly known as the ring network cabinet, is specifically designed for power systems operating at an AC frequency of 50Hz and a voltage of 12kV. This reliable equipment is ideal for both industrial and civilian cable ring networks, as well as power supply terminals.
Widely utilized across various applications, including small secondary substations, switching stations, urban residential distribution, and industrial environments, our switchgear is perfect for shopping malls, airports, subways, wind power generation, hospitals, sports venues, railways, and more. As a leading China supplier and factory, we ensure that our products meet the highest quality standards while providing efficient and robust solutions for your power distribution needs.

,

    Model and Definitions
    Model and Definitions
    Application Conditions
    • Altitude: ≤1000m (If there are special requirements, please specify when placing an order. Currently, there are 6 sets operating at an altitude of 5200m.)
    • Ambient Temperature: -35℃ to 45℃, with a maximum daily average temperature difference of ≤25℃.
    • Daily relative humidity should not exceed 95%, and monthly average relative humidity should not exceed 90%.
    • Seismic Resistance: 8 degrees
    • It should be used in areas without severe vibrations and shocks, and where there is no risk of fire, chemical corrosion, or explosion.
    Standards
    • GB3906-2006 "AC Metal-Enclosed Switchgear and Controlgear for 3.6 kV to 40.5 kV"
    • IEC 60298-1990 "AC Metal-Enclosed Switchgear and Controlgear for Nominal Voltage Above 1kV and Below 52kV"
    • GB/T11022-2011 "Common Technical Requirements for High-Voltage Switchgear and Controlgear Standards"
    Structural Brief
    No. ltems Units Value
    1 Nominal Voltage KV 12
    2 Rated Frequency Hz 50
    3 Main Bus Rated Current/Maximum Rated Current of Fuse A 630, 125
    4 Main Circuit, Ground Circuit Rated Short-Time Withstand Current KA/S 20, 3
    5 Main Circuit, Ground Circuit Rated Peak Withstand Current of Main KA 50
    6 Rated Short-Circuit Closing Current of Main Circuit and Ground Circuit KA 50
    7 Full Capacity Breaking Number of Load Switch Time 100
    8 Breaking Current of Fuse KA 31.5, 40
    9 Rated Closed Loop Breaking Current A 630
    10 Rated Transfer Current A 1600
    11 Machinery Service Life Time 2000
    12 1 Minute Power Frequency Withstand Voltage (Peak Value) Relative to Ground/lsolation Break KV 42, 48
    13 Lightinglmpulse Withstand Voltage (Peak Value) Phase-to-Phase, Relative to Ground/lsolation Break KV 75, 85
    14 1 Minute Power Frequency Withstand Voltage of Time Circuit KV 2
    15 Level of Protection IP3X
    Dimensions
    Dimension Type Dimensions (mm) Scope of Application
    Height H 1400 Suitable for Single-core Electric Cable
    1600 Suitable for Single-core Electric Cable
    1800 Suitable for Three-core Electric Cable
    Width W 375 Incoming Line & Outcoming Line
    500 -
    750 -
    Depth D 918 -
    Structural Brief
    Structural Brief
    Frequently Asked Questions
    What is the standard altitude limit for this switchgear?

    The standard altitude limit is ≤1000m. However, customized units can be designed for higher altitudes, with 6 sets currently operating successfully at 5200m.

    What are the environmental temperature requirements?

    The equipment operates reliably in ambient temperatures from -35℃ to 45℃, with a maximum daily average temperature difference of ≤25℃.

    Which standards does this switchgear comply with?

    It strictly complies with GB3906-2006, IEC 60298-1990, and GB/T11022-2011 standard specifications.

    What is the protection level of the enclosure?

    This metal-enclosed switchgear features an IP3X level of protection to prevent ingress of foreign objects.

    What are the available width options for different applications?

    The width options are 375mm, 500mm, and 750mm. The 375mm width is typically applied for standard incoming and outcoming lines.

    Are there any environmental restrictions for installation?

    Yes, it should be installed in areas free from severe vibrations, physical shocks, fire hazards, chemical corrosion, or explosion risks.