Leave Your Message

China HXGN15-12 Box-Type Fixed AC Metal-Enclosed Switchgear - Reliable Suppliers and Factory Solutions

,

Overview

,

Introducing the HXGN15-12 box-type fixed metal-enclosed ring network switchgear, also known as the ring network cabinet, designed specifically for power systems operating at an AC frequency of 50Hz and a voltage of 12kV. This innovative equipment is ideal for industrial and civilian cable ring networks, serving as a reliable power supply terminal.
Our ring network switchgear is highly suitable for small secondary substations, switch stations, urban residential distribution, and various applications in industrial and mining enterprises, shopping malls, airports, subways, wind power generation facilities, hospitals, sports venues, railways, and more. As a leading China manufacturer and supplier, we ensure that our products meet the highest standards of quality and efficiency, making us the preferred choice for businesses looking for reliable power solutions.

,

    Model and Definitions

    Model and Definitions Diagram

    Application Conditions

    Altitude: ≤1000m (Special requirements can be customized upon order. Currently, 6 sets are operating successfully at an altitude of 5200m.)
    Ambient Temperature: -35℃ to 45℃, with a maximum daily average temperature difference of ≤25℃.
    Relative Humidity: Daily average should not exceed 95%, and monthly average should not exceed 90%.
    Seismic Resistance: Class 8
    Environment: Suitable for areas free from severe vibrations, shocks, fire hazards, chemical corrosion, or explosion risks.

    Standards

    GB3906-2006 "AC Metal-Enclosed Switchgear and Controlgear for 3.6 kV to 40.5 kV"
    IEC 60298-1990 "AC Metal-Enclosed Switchgear and Controlgear for Nominal Voltage Above 1kV and Below 52kV"
    GB/T11022-2011 "Common Technical Requirements for High-Voltage Switchgear and Controlgear Standards"

    Structural Brief

    No. Items Units Value
    1 Nominal Voltage KV 12
    2 Rated Frequency Hz 50
    3 Main Bus Rated Current/Maximum Rated Current of Fuse A 630,125
    4 Main Circuit, Ground Circuit Rated Short-Time Withstand Current KA/S 20,3
    5 Main Circuit, Ground Circuit Rated Peak Withstand Current of Main KA 50
    6 Rated Short-Circuit Closing Current of Main Circuit and Ground Circuit KA 50
    7 Full Capacity Breaking Number of Load Switch Time 100
    8 Breaking Current of Fuse KA 31.5,40
    9 Rated Closed Loop Breaking Current A 630
    10 Rated Transfer Current A 1600
    11 Machinery Service Life Time 2000
    12 1 Minute Power Frequency Withstand Voltage (Peak Value) Relative to Ground/Isolation Break KV 42,48
    13 Lightning Impulse Withstand Voltage (Peak Value) Phase-to-Phase, Relative to Ground/Isolation Break KV 75,85
    14 1 Minute Power Frequency Withstand Voltage of Time Circuit KV 2
    15 Level of Protection - IP3X

    Dimensions

    Dimension Parameter Value (mm) Scope of Application
    Height H 1400 Suitable for Single-core Electric Cable
    1600 Suitable for Single-core Electric Cable
    1800 Suitable for Three-core Electric Cable
    Width W 375 Incoming Line & Outcoming Line
    500 -
    750 -
    Depth D 918 -

    Structural Brief

    Structural Design Diagram

    Frequently Asked Questions (FAQ)

    Can this switchgear be used in high-altitude environments?
    Yes. While the standard design is rated for altitudes ≤1000m, special customizations are available. Currently, there are 6 sets operating reliably at an altitude of 5200m. Please specify your requirements when placing an order.
    What standards does this switchgear comply with?
    The switchgear complies with major national and international standards, including GB3906-2006, IEC 60298-1990, and GB/T11022-2011.
    What is the IP protection level of this equipment?
    This switchgear features an IP3X level of protection, which ensures sufficient safety against external solid objects.
    What are the temperature and humidity limits for normal operation?
    It operates within an ambient temperature range of -35℃ to 45℃ (daily average difference ≤25℃). The daily relative humidity should not exceed 95%, and the monthly average relative humidity should not exceed 90%.
    How do I choose the correct height dimension for my cabling?
    The height of the unit depends on your cable configuration: 1400mm and 1600mm heights are suitable for single-core electric cables, whereas the 1800mm height is recommended for three-core electric cables.