Leave Your Message

China GZDW DC Power Cabinet - Reliable Solutions from Leading Suppliers and Factory for Power Plants and Substations

,

Overview

,

The GZDW Series DC Power Cabinets are essential components for a wide range of applications in power plants and substations, accommodating large, medium, and small facilities. These cabinets facilitate high-voltage switch operations, relay protection, automatic control, and provide the necessary DC power for lighting and signaling systems. Beyond power generation, these cabinets find utility in various sectors including metallurgy, railways, mining, petrochemicals, telecommunications, healthcare, banking, hospitality, high-rise buildings, and computer networks. Our microcomputer-controlled DC power cabinets are designed for unmanned operations, enabling centralized remote monitoring for power plants, substations, and other industrial uses. Manufactured in China, our products adhere to the JB/T57774-2000 standard, which outlines the General Technical Conditions and Safety Requirements for DC Power Equipment in Power Systems. As a leading factory and supplier, we are committed to delivering high-quality solutions tailored to your energy needs.

,

    Model and Definitions

    product-description1

    Application Conditions

    Altitude: no more than 2000m.
    Ambient temperature: -5℃~+40℃.
    Relative Humidity: not more than 90%. (at 20+5℃)
    Note: Special conditions can be negotiated with our company

    Technical Reference

    Input Power Voltage: Three-phase AC 380V±10%, 50Hz±5% ;
    Output DC voltage rating: 24v; 48v; 110v; 220v;
    Output DC current rating: 5A, 8A, 10A, 15A, 20A, 30A, 40A, 50A, 80A, 100A, 150A, 200A, 250A .
    Battery Rated Capacity: 10Ah, 20Ah, 38Ah, 40Ah, 50Ah, 60Ah, 65Ah, 80Ah, 100Ah, 150Ah, 200Ah, 250Ah, 300Ah, 400Ah.
    Voltage adjustment range (see table below)
    Output DC current adjustment range: 0~100% of rated value
    Stable accuracy <±1%
    Steady current accuracy <±1%
    Ripple coefficient: <1%
    Machine noise: <55dB
    Main transformer temperature rise: 70℃
    Working mode: continuous working
    Efficiency>90%
    Level of Protection: IP20~IP30
    Output DC voltage rating 24V 48V 110V 220V
    Float charge voltage adjustment range 21-28 43-57 99-130 198-260
    Equalizing charging voltage adjustment range 27-31 54-62 125-140 198-286
    Main charging voltage adjustment range 21-36 43-70 99-162 187-310

    Product appearance and installation dimensions

    product-description2
    Frequently Asked Questions (FAQ)
    Q1: What are the standard application conditions for this device?
    A: The standard conditions require an altitude of no more than 2000m, an ambient temperature range of -5℃ to +40℃, and relative humidity not exceeding 90% (at 20±5℃). Special conditions can be customized and negotiated.
    Q2: What is the input power voltage and frequency range?
    A: The system requires a three-phase AC 380V±10% input power voltage with a frequency of 50Hz±5%.
    Q3: What are the available output DC voltage and current ratings?
    A: The rated output DC voltages are 24V, 48V, 110V, and 220V. The rated output DC current options range from 5A up to 250A to suit different capacity requirements.
    Q4: Can the output DC current be adjusted?
    A: Yes, the output DC current is fully adjustable from 0% to 100% of its rated value.
    Q5: What is the protection level and efficiency of this machine?
    A: The machine operates at a high efficiency of over 90% and offers an IP20 to IP30 level of protection.
    Q6: What are the noise levels and temperature rise limits?
    A: The machine operates quietly with noise levels under 55dB, and the temperature rise of the main transformer is limited to 70℃ during continuous operation.