Leave Your Message

China GTXGN-12 AC Metal Solid Insulated Ring Main Unit - Reliable Suppliers and Factory for High-Voltage Solutions

,

Overview

,

The GTXGN-12 AC Metal Solid Insulated Ring Main Unit is an innovative solution designed by leading China suppliers, featuring a fully insulated and maintenance-free solid insulated vacuum switchgear device. This high-performance unit encapsulates all high-voltage live components in high-quality epoxy resin materials, integrating the vacuum arc extinguishing chamber, main conductive circuit, and insulating support into one compact system. The fully insulated solid busbars connect the functional units, enhancing the unit's reliability and ensuring safety for personnel by protecting it from external environmental factors.

,

This ring main unit boasts a simple structure, flexible operation, reliable interlocking mechanisms, and easy installation. It is engineered for a 50Hz, 12 kV power system and is extensively used in industrial and civilian cable ring networks, as well as distribution terminal projects. It is ideal for urban residential area distribution, small substations, switching stations, cable branching boxes, box-type substations, and various locations including shopping malls, airports, subways, wind power plants, hospitals, stadiums, railways, and tunnels.

,

Thanks to its fully insulated, completely sealed, and fully shielded design, this product excels in harsh environments such as high altitudes, extreme temperatures, high humidity, and areas with significant pollution. As a trustworthy factory in China, we are committed to providing high-quality, robust solutions for all your electrical distribution needs.

,

    Product Categories

    The switches are categorized based on type into Load Switch with Ground Assembly (C Module), Load Switch without Ground Assembly (CB Module), Circuit Breaker with Ground Assembly (V Module), Circuit Breaker without Ground Assembly (VB Module), Circuit Breaker Link Switch (VZ Module), Load Switch + Fuse Composite Apparatus Switch Assembly (F Module), and Isolating Switch Assembly (G Module).

    Model and Definitions

    product-description1

    Application Conditions

    Environmental Temperature:
    -45℃ to +45℃
    Humidity:
    Max Average Relative Humidity, Daily Average≤95%, Monthly Average≤90%
    Altitude:
    ≤4000 meters
    Seismic Resistance:
    8 degrees
    Level of Protection:
    Live Parts Sealed IP67, Fuse Tubes IP67, Switch Cabinet Housing IP4X

    Standards for Implementation

    IEC62271-1-2007 "High-Voltage Switchgear and Controlgear - Part 1: General Specifications"
    IEC620071-200-2003 "AC Metal-Enclosed Switchgear and Controlgear for 1-52kV"
    GB3906-2006 "AC Metal-Enclosed Switchgear and Controlgear for 3.6-40.5kV"
    GB/T11022-1999 "Common Technical Conditions for High-Voltage Switchgear and Controlgear Standards"
    GB1984-2003 "High-Voltage AC Circuit Breakers"
    GB1985-2004 "High-Voltage AC Disconnectors and Earthing Switches"
    GB3804-2004 "High-Voltage AC Load Switches for 3.6kV to 40.5kV"
    DL/T404-2007 "AC Metal-Enclosed Switchgear and Controlgear for 3.6kV-40.5kV"
    DIJT5932006 "Common Technical Conditions for High-Voltage Switchgear and Controlgear Standards"
    Q/GDW730-2012 "Technical Conditions for 12kV Solid Insulated Ring Main Units"

    Technical Parameters

    Parameters of Switchgear
    No. Units Parameters
    Nominal Voltage KV 12
    Rated Frequency Hz 50
    Rated Currency A 630 1250
    Nominal Insulation Level Power Frequency Withstand Voltage Break Point KV 48
    Phase-to-Phase KV 42
    Relative KV 42
    Lighting lmpulse Withstand Voltage Break Point KV 85
    Phase-to-Phase KV 75
    Relative KV 75
    Rated Short-circuit Breaking Current(1s) KA 25 31.5
    Rated Short-time Withstand Current(4s) KA 25 31.5
    Rated Peak Withstand Current(lp) KA 36 80
    Rated Circuit Making Current(Peak)(1ma) KA 36 80
    Level of Protection for Shell IP4X
    Operation Mode Spring-operated
    Isolation Ground Switch Technical Parameters
    No. ltems Units Parameters
    1 Nominal Voltage kV 12
    2 Rated Currency A 630 1250
    3 4S Rated Short-time Withstand Current (Valid Value) kA 25 31.5
    4 Rated Peak Withstand Current (Peak) kA 63 80
    5 1min Power Frequency Withstand Voltage Phase-to-Phase and Ground kV 42
    lsolation Break Point 48
    6 Rated Lighting lmpulse Withstand Voltage Phase-to-Phase and Ground kV 75
    lsolation Break Point 85
    7 Main Switch Machinery Service Life Time 3000
    8 Ground Switch Machinery Service Life Time 3000

    Safety and Environmental Protection

    Isolation Knife Visible Break Point
    The cabinet features a prominent visible window for the Isolation Break Point, allowing personnel to observe the three working positions: isolation engaged, isolation disengaged, and grounding engaged. This design facilitates the on-site staff in determining the position of the isolation knife, ensuring a high level of safety.
    Internal Arc Design
    Internal Arc Pressure Valve: When an arc occurs inside the product, the pressure will be released through this valve, directing the arc away into the cable trench to prevent accidental injury to operators.
    Green & Environmental Friendly
    Designed with environmentally friendly materials, this product does not use SF6 gas as an arc extinguishing medium or insulation, thus avoiding environmental pollution. The one-time circuit design minimizes contact points, ensuring low energy consumption during operation.

    External Dimensions

    product-description2
    Model Width (mm) Depth(mm) Height(mm)
    Load Switch PT Cabinet (CPT) 500 950 1650
    Circuit Breaker Cabinet (VB) 400 950 1650
    Circuit Breaker Cabinet(V) 400 950 1650
    Circuit Breaker Bus Coupling Cabinet (VZ) 400 950 1650
    Busbar Lifting Cabinet(G) 400 950 1650
    Load Switch Fuse Combination Cabinet (F) 500 950 1650

    Frequently Asked Questions

    What module options are available for these product categories?
    The switches are categorized based on type into Load Switch with Ground Assembly (C Module), Load Switch without Ground Assembly (CB Module), Circuit Breaker with Ground Assembly (V Module), Circuit Breaker without Ground Assembly (VB Module), Circuit Breaker Link Switch (VZ Module), Load Switch + Fuse Composite Apparatus Switch Assembly (F Module), and Isolating Switch Assembly (G Module).
    What are the required environmental application conditions?
    The equipment operates under environmental temperatures of -45℃ to +45℃, maximum daily relative humidity ≤95% (monthly ≤90%), altitudes up to 4000 meters, seismic resistance of 8 degrees, and protection levels of IP67 for live sealed parts/fuse tubes and IP4X for the cabinet housing.
    How does the switchgear design ensure operator safety during an internal arc event?
    The switchgear includes an Internal Arc Pressure Valve. In the event of an internal arc, the pressure is released through this valve, directing the arc away into the cable trench to prevent accidental injury to nearby operators.
    Why is this product considered green and environmentally friendly?
    It uses environmentally friendly materials and completely avoids SF6 gas as an arc extinguishing medium or insulation. Additionally, the one-time circuit design reduces contact points, leading to lower energy consumption during operations.
    What is the mechanical service life of the main and grounding switches?
    Both the Main Switch and the Ground Switch have a rated mechanical service life of 3000 operations.
    What are the dimensions of the Circuit Breaker Cabinet (VB)?
    The Circuit Breaker Cabinet (VB) has a width of 400 mm, a depth of 950 mm, and a height of 1650 mm.