China GCS AC Low Voltage Switchgear Suppliers - Factory Direct Distribution Solutions for Industries

,

Overview
The GCS device is an essential solution for power distribution systems across various industries, including power plants, petroleum, chemical, metallurgy, textiles, and high-rise buildings. Designed to meet the demands of large power plants and petrochemical facilities with advanced automation needs, this device provides a low-voltage complete distribution solution for power supply, centralized motor control, and reactive power compensation. Operating at a three-phase AC frequency of 50(60)Hz, it supports a Rated Working Voltage of 380V(400V) or (660V) and accommodates a Rated Current of 4000A and below. As a leading choice among China suppliers, our factory ensures top quality and reliability in every GCS device, making it an ideal option for your industrial power distribution needs.

,

    Model and Definitions

    Model and Definitions

    Performance Indexes

    ◆ The design of the device complies with the following standards:
    ◇ IEC 439-1: Low-voltage switchgear and controlgear assemblies
    ◇ GB 7251: Low-voltage switchgear and controlgear assemblies
    ◇ ZBK 36001: Low-voltage withdrawable switchgear assemblies

    Basic Parameters

    Main Current Nominal Voltage(V) AC 380(4000),(660) Exchange 380(400)、(660)
    Auxiliary Circuit Nominal Voltage(V) AC 220、380(400)
    DC (110、220)
    Rated Frequency(Hz) 50(60)
    Rated Insulation Voltage (V) 660 (1000)
    Rated Currency(A) Horizontal Busbar ≤4000
    Vertical Busbar (MCC) 1000
    Bus Rated Short-time Withstand Current(kA,1s) 50,80
    Bus Rated Peak Withstand Current(kA/0.1s) 105,176
    Power Frequency Test Voltage (V/1min) Main Circuit 2500
    Auxiliary Circuit 1760
    Bus Three-phase Four-wire System A.B.C.PE.N
    Three-phase Five-wire System A.B.C.PE.N
    Level of Protection IP30.IP40

    Installation Features

    ◇ Improving the thermal capacity of transfer components significantly reduces the additional temperature rise caused by the temperature increase in connectors, cable heads, and partition plates.
    ◇ The segregation between functional units and compartments is clear and reliable. This ensures that the failure of one unit does not affect the operation of others, thus confining faults to the smallest possible scope.
    ◇ The horizontal arrangement of busbars enhances the device's dynamic thermal stability, allowing it to withstand short-circuit current impacts of 80/176 kA.
    ◇ Furthermore, the Motor Control Center (MCC) cabinets can accommodate up to 22 circuits each, fully considering the needs of large-capacity power generation and automation of electric motor clusters in industries such as petrochemicals.
    ◇ Connections between the device and external cables are completed within the cable compartment, allowing cables to enter and exit from either the top or bottom. Current transformers are installed within the cable compartment, facilitating easy installation and maintenance.
    ◇ Within the same Power distribution system, current-limiting reactors can be utilized to match and limit short-circuit currents, stabilizing busbar voltage at a specific value. This can also partially reduce the short-circuit strength requirements for components.
    ◇ Lastly, drawer units are equipped with a sufficient number of secondary connectors (32 pairs for one unit or more, and 20 pairs for half units), meeting the connection point requirements for computer interfaces and automatic control circuits.

    Auxiliary Electric Devices

    The design of auxiliary circuit diagrams complies with the "Technical Specifications for Power Supply Design of Thermal Power Plants" and other relevant design technical regulations. It is suitable for low-voltage power supply systems in power plants, substations, as well as low-voltage distribution systems in industrial enterprises and high-rise buildings.
    The auxiliary circuit scheme is designed based on the main circuit scheme, divided into functional units for Power incoming lines, feeder lines (PC), and motor feeder lines (MCC) for operational control.

    Installation Schematic Diagram

    Installation Schematic Diagram
    Cabinet No. A B C D remarks
    GCS-TG1010-4 1000 1000 850 956 Contact Cabinet
    GCS-TG0810-4 800 800 650 956 Power receiving cabinet
    GCS-TG0808-4 800 800 650 756 Power receiving cabinet
    GCS-TG0608-4 600 600 450 756 Power receiving cabinet

    Fig. 2 PC Cabinet Installation Schematic Diagram

    Fig. 2 PC Cabinet Installation Schematic Diagram
    Cabinet No. A B C D E FXG
    GCS-TG1010-2 1000 1000 850 956 60 400x400
    GCS-TG0810-2 800 1000 650 956 160 200x400
    GCS-TG0808-2 1000 800 850 756 60 400x400
    GCS-TG0608-2 800 800 650 756 160 200x400

    Fig. 3 MCC Cabinet Installation Schematic Diagram

    Fig. 3 MCC Cabinet Installation Schematic Diagram
    Cabinet No. A B C D E FXG
    GCS-TG1006-1 1000 600 850 556 60 400x350
    GCS-TG0806-1 800 600 650 556 160 200x350

    Ordering Notices

    ◆ The order contract includes the following contents:
    ◇ The complete model of the product, including the main circuit scheme number and auxiliary circuit scheme number.
    ◇ The main circuit system combination sequence diagram
    ◇ The electrical schematic diagram of the auxiliary circuit.
    ◇ A list of components within the cabinet.
    ◇ Setting parameters for voltage, current, time, and other relevant factors in the circuit.
    ◇ Any other special requirements that do not conform to the normal use of the product.

    Frequently Asked Questions (FAQ)

    What standards do these low-voltage switchgear assemblies comply with?

    The design of the device fully complies with international and national standards, including IEC 439-1, GB 7251, and ZBK 36001.

    What is the rated insulation voltage and protection level of the system?

    The rated insulation voltage is 660V (up to 1000V), and the ingress protection level is rated at IP30 or IP40.

    How does the cabinet design prevent fault propagation?

    Clear and reliable segregation between functional units and compartments ensures that a failure in one unit does not affect the operation of others, confining faults to the smallest possible scope.

    What is the short-circuit strength capability of the busbar system?

    The horizontal arrangement of the busbars enhances dynamic thermal stability, allowing the device to withstand rated short-time withstand currents of 50/80 kA (1s) and peak withstand currents of 105/176 kA.

    What information is required when placing an order?

    Orders require the complete product model (including main and auxiliary circuit scheme numbers), main circuit combination sequence diagram, auxiliary circuit electrical schematic, component list, specific voltage/current/time parameter settings, and details of any special requirements.