China DFW Switched Cable Branch Box - Reliable Factory Suppliers for Durable Power Solutions

,

Functional Characteristics

,

This advanced product features prefabricated, touch-safe silicone rubber cable terminals that are fully sealed, insulated, and maintenance-free, ensuring optimal personal safety. Its compact design boasts an aesthetically pleasing appearance, highlighted by a double-layer stainless steel body known for its durability, lasting over twenty years. The system allows for maintenance during regional power outages without interrupting the main network operation, effectively minimizing the impact of power outages.

,

Designed with flexibility in mind, it can accommodate one or multiple SF6 Load Switches, while offering diverse wiring methods that support up to 8 branch outgoing circuits. Additionally, our solutions are tailored to meet varied user requirements, with options for surge protectors, short-circuit fault indicators, and current-limiting fuses. As a leading China factory and supplier, we deliver high-quality products designed to enhance efficiency and performance in power management.

,

    Model and Definitions
    DFW Technical Parameters
    No. Items Parameters
    1 Nominal Voltage 12kV
    2 Rated Currency 630A
    3 Power Frequency Withstand Voltage (Phase to Ground) 42kV/min
    4 Lightning lmpulse Voltage 75kV
    5 Rated Breaking Current 630A
    6 Rated Short-circuit Making Current(Peak Value) 50kA
    7 Rated Short-time Withstand Current 25kA/4S
    8 Rated Peak Withstand Current 50kA
    9 Rated Peak Withstand Current 45A
    10 Rated Breaking Capacitive Current 16A
    11 Full Load Breaking Time >100
    12 Mechanical Operation Time for Opening and Closing 2000
    External Schematic Diagram
    Basic Structure
    Technical Requirements
    ◇ The inner side of the brick wall is to be sealed with a 1:3 cement mortar mix and treated for waterproofing.
    ◇ Beam penetrations should use φ6 concrete operations.
    ◇ The foundation channel steel must undergo anti-corrosion treatment after fabrication.
    ◇ After the installation of the branch box is completed, the area around the base should be sealed with cement.
    ◇ Waterproof measures must be taken at the manhole entrance.
    ◇ Grounding electrodes should be pre-embedded in the foundation, with grounding resistance meeting the requirements set by the power department.
    Ordering Instructions
    ◇ The product model and any special requirements from the user can provide a one-time diagram.
    ◇ The standard cross-sections for incoming and outgoing lines and branch cables.
    ◇ The quantity of optional surge protectors and short-circuit fault indicators.
    Frequently Asked Questions (FAQ)
    Q: What is the nominal voltage and rated current of the DFW unit?
    A: The DFW unit operates with a nominal voltage of 12kV and a rated current of 630A.
    Q: What foundation preparation is needed before installation?
    A: The foundation requires a 1:3 cement mortar waterproof coating on the inner brick wall, anti-corrosion treated channel steel, and pre-embedded grounding electrodes compliant with power department regulations.
    Q: How many mechanical operations can the equipment endure?
    A: The equipment is rated for up to 2000 mechanical operations for opening and closing cycles.
    Q: What details must be specified when placing an order?
    A: Buyers need to specify the product model, single-line diagram (one-time diagram), cable cross-section dimensions for main/branch lines, and quantities for optional surge arresters or fault indicators.
    Q: What are the waterproofing requirements for the installation site?
    A: Waterproofing treatment must be applied to the inner brick walls, base perimeter sealed with cement after setup, and reliable waterproof measures implemented at the manhole entrance.